WAGO-I/O-SYSTEM 750
Diagnostics
67
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
Pos: 83 /Alle Serien (Allgemeine Module)/Überschriften für alle Serien/Diagnose - Service/Diagnose - Überschrift 1 @ 4\mod_1240831069471_21.doc @ 31372 @ 1 @ 1
10 Diagnostics
Pos: 84 /Serie 750 (WAGO-I/O-SYSTEM)/Diagnose/Feldbuskoppler/-controller/Diagnose 750-0657 @ 9\mod_1296727922797_21.doc @ 69150 @ 223 @ 1
The IO-Link master provides two options for diagnosis and event handling – via
the status byte and the Mailbox.
Diagnosis via PROFIBUS coupler is found in the appendix in section "Fieldbus-
Specific Additions" > "PROFIBUS" > "Diagnosis When Using a PROFIBUS
Coupler".
10.1
Diagnosis via the Status Byte
If register communication is disabled (bit 7 in the control byte = 0), status
information of the I/O module and IO-Link ports is displayed via the status byte.
Table 30: Status byte
Status byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0 GEN_
ERR
PORT4_
ERR
PORT3_
ERR
PORT2_
ERR
PORT1_
ERR
IOLM_
ERR
INT_
ERR
1
Res.
Register number of the request (mirrored)
0 Mailbox
active
(Bit 7)
1 Register communication active
0 No
error
GEN_ERR
1 Error is pending. Set when one of the bits 0…5 = 1.
0 The device attached to port 4 is not in the fault condition.
PORT4_ERR
1 The device attached to port 4 is in the fault condition.
0 The device attached to port 3 is not in the fault condition.
PORT3_ERR
1 The device attached to port 3 is in the fault condition.
0 The device attached to port 2 is not in the fault condition.
PORT2_ERR
1 The device attached to port 2 is in the fault condition.
0 The device attached to port 1 is not in the fault condition.
PORT1_ERR
1 The device attached to port 1 is in the fault condition.
0 The IO-Link master is not in the fault condition.
IOLM_ERR
1 The IO-Link master is in the fault condition.
0 No internal errors
INT_ERR
1 Internal error. Possible causes:
• 24V field supply missing
• Communication via mailbox and process data faulty.