WAGO-I/O-SYSTEM 750
Diagnostics
69
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
0x00 Cancel_DiagMsg_Request
0x01 Idle_Request
0x02 Send_DiagMsg_Request
Service ID
0x03 …0xFF
Reserved
Sequence ID
0x00…0xFF
Used to distinguish successive requests and to assign to the response
Event Code
0x0000…0xFFFF Event code of the diagnostic message
(see the following section)
0x00 IO-Link
master
0x01 Port
1
0x02 Port
2
0x03 Port
3
0x04 Port
4
Channel Number
0x05…0xFF Reserved
Bit 7…Bit 6
Event mode:
0x0: Reserved
0x1: Single Shot
0x2: Event disappears
0x3: Event appears
Bit 5…Bit 4
Event type:
0x0: Reserved
0x1: Information
0x2: Warning
0x3: Error
Bit 3
SOURCE
0 Device application (remote)
1 Master application (local)
Event Qualifier
Bit 2…Bit 0
Event instance:
0x0: Unknown
0x1: Physical Layer
0x2: Data Link Layer
0x3: Application Layer
0x4: Application
0x5 – 0x7: Reserved
Pos: 85 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1