WAGO-I/O-SYSTEM 750
Diagnostics
73
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
10.3.2
Event Codes of Attached Devices
The following list provides an overview of event codes according to the IO-Link
specification. Which of these event codes are supported by the attached IO-Link
device is defined in the respective device documentation or device-specific IODD.
Table 33: Error codes acc. IO-Link specification
Code hex.
Description
Device
State
Type
0000 No
malfunction
0
N
1000
General malfunction – unknown error
4
E
1001 – 17FF
Reserved
1800 – 18FF
Manufacturer / vendor specific
1900 – 3FFF
Reserved
4000
Temperature fault – Overload
4
E
4001 – 420F
Reserved
4210 Device
temperature
over-run – Clear source of heat
2
W
4211 – 421F
Reserved
4220
Device temperature under-run – Insulate Device
2
W
4221 – 4FFF
Reserved
5000
Device hardware fault – Device exchange
4
E
5001 – 500F
Reserved
5010
Component malfunction – Repair or exchange
4
E
5011
Non volatile memory loss – Check batteries
4
E
5012
Batteries low – exchange batteries
2
W
5013 – 50FF
Reserved
5100
General power supply fault – Check availability
4
E
5101
Fuse blown/open – Exchange fuse
5102 – 510F
Reserved
5110
Primary supply voltage over-run – Check tolerance
2
W
5111
Primary supply voltage under-run – Check tolerance
2
W
5112
Secondary supply voltage fault (Port Class B) – Check
tolerance
2 W
5113 – 5FFF
Reserved
6000
Device software fault – Check firmware revision
4
E
6001 – 631F
Reserved
6320
Parameter error – Check data sheet and values
4
E
6321
Parameter missing – Check data sheet
4
E
6322 – 634F
Reserved
6350
Parameter changed – Check configuration
4
E
6351 – 76FF
Reserved
7700
Wire break of a subordinate device – Check installation
4
E
7701 – 770F
Wire break of subordinate device 1 … device 15 – Check
installation
4 E
7710
Short Circuit – Check installation
4
E
7711
Ground fault – Check installation
4
E
7712 – 8BFF
Reserved
8C00
Technology specific application fault – Reset Device
4
E
8C01
Simulation active – Check operational mode
3
W
8C02 – 8C0F
Reserved
8C10
Process variable range over-run – Process Data uncertain
2
W
8C11 – 8C1F
Reserved