74 Diagnostics
WAGO-I/O-SYSTEM
750
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
Table 33: Error codes acc. IO-Link specification
Code hex.
Description
Device
State
Type
8C20
Measurement range over-run – Check application
4
E
8C21 – 8C2F
Reserved
8C30
Process Variable Range under-run – Process Data
uncertain
2 W
8C31 – 8C3F
Reserved
8C40
Maintenance required – Cleaning
1
N
8C41
Maintenance required – Refill
1
N
8C42
Maintenance required – Exchange wear and tear parts
1
N
8C43 – 8C9F
Reserved
8CA0 – 8DFF
Manufacturer / vendor specific
8E00 – AFFF
Reserved
B000 – BFFF
Reserved for profiles
C000 – FEFF
Reserved
FF00 – FFFF
SDCI specific Event codes
N Notification
W Warning
E Error
Device State 0 Device is OK
Device State 1 Maintenance-Required
Device State 2 Out-of-Specification
Device State 3 Functional-Check
Device State 4 Failure