WAGO-I/O-SYSTEM 750
Appendix 109
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
11.3.1.2 COM_MODE
The COM_MODE data field indicates which modes of communication are
available in IO-Link mode. The value COM3 (230.4 kBaud) includes the slower
modes COM2 (38.4 kBaud) and COM1 (4.8 kBaud).
Table 77: IOL-M Basic Configuration, COM_MODE
Name
Data type
Access
Value
COM_MODE UNSIGNED8 ro
0x03
The following table provides an overview of the data structure.
Table 78: COM_MODE, Data structure
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0 0 0 0 0 0 COM_MODE
Table 79: COM_MODE, Description
Bit field
Access
Value Description
0 Reserved
1
The IO-Link master supports max. COM1 (4.8 kBaud).
2
The IO-Link master supports max. COM2 (38.4 kBaud)
and COM1 (4.8 kBaud).
COM_MODE
ro
3
The IO-Link master supports max. COM3 (230.4 kBaud),
COM2 (38.4 kBaud) and COM1 (4.8 kBaud).
11.3.1.3 MASTER_MIN_CYCL
The MASTER_MIN_CYCL data field indicates the shortest time frame with
which the I/O module queries the attached IO-Link devices. Slower devices are
queried at a slower speed.
Table 80: IOL-M Basic Configuration, MASTER_MAX_CYCL
Name
Data type
Access
Value
MASTER_MIN_CYCL
UNSIGNED8 ro
0x11 (corresponds to 1.7ms)
The following provides an overview of the structure:
Table 81: MASTER_MIN_CYCL, Data structure
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
TIMEBASE MULTIPLIER