WAGO-I/O-SYSTEM 750
Configuration and Parameterization
53
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
9.1.1.2.3.2 Diagnoses/Errors
Figure 23: Display of diagnostic and error messages
Table 22: Display of diagnostic and error messages
Option
Description
Timestamp
Message timestamp
Type
Message type: “Error”, “Warning” or “Message”
Channel
Master, Port 1, Port 2, Port 3, Port 4
Mode
Unconfirmed message “Single shot“, “Appear“, “Disappear“
Source
Master/Appl. or Device
Instance
Event instance:
0: Unknown
1: Physical layer
2: Data link layer
3: Application layer
4: Application
Event Code
Event code hexadecimal (see table "Event Codes of the IO-Link Masters")
Description
Description of the diagnostic message or event
IOLM-Error
IOL master error code (see section "Error Messages")
IOLD-Error
IOL device error code (see section "Error Messages")
FI-Index
Specification of the record to be accessed (see section "FI_Index")
Port
Master, Port 1, Port 2, Port 3, Port 4
Diagnostic and error messages are also displayed at the bottom of the window on
the configuration pages.
Pos: 78.4 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1