WAGO-I/O-SYSTEM 750
Appendix
97
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
Overview of allowed error types "IOL_D_error_code" (column 1) and
"IOL_D_add_error_code" (column 2):
Pos: 92 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
Table 64: IOL_D_error_code, IOL_D_add_error_code
Error
code
Additional
code
Designation
Cause
Possible
solution*
0x10 0x00
COM_ERR
Communication
error
(1)
0x56
0x00
M ISDU CHECKSUM
Master – ISDU checksum error (1)
0x57 0x00
M_ISDU_ILLEGAL Master – ISDU, illegal service
element
(1)
0x80 0x00
APP_DEV
Device
program
error
(2)
0x80
0x11
IDX_NOTAVAIL
Index is not available
(3)
0x80
0x12
SUBIDX_NOTAVAIL
Subindex is not available
(3)
0x80 0x20
SERV_NOTAVAIL Service is currently not
available
(4)
0x80 0x21
SERV_NOTAVAIL_
LOCCTRL
Master service is currently not
available
(5)
0x80 0x22
SERV_NOTAVAIL_
DEVCTRL
Device service is currently not
available
(4)
0x80 0x23
IDX_NOT_
WRITABLE
Access denied
(3)
0x80
0x30
PAR_VALOUTOFRNG Parameter not in value range
(6)
0x80
0x31
PAR_VALGTLIM
Parameter value upper limit
(6)
0x80
0x32
PAR_VALLTLIM
Parameter value lower limit
(6)
0x80
0x33
VAL_LENOVRRUN
Parameter value too long
(6)
0x80
0x34
VAL_LENUNDRUN
Parameter value too short
(6)
0x80
0x35
FUNC_NOTAVAIL
Function is not available
(4)
0x80 0x36
FUNC_
UNAVAILTEMP
Function is temporarily not
available
(4)
0x80
0x40
PAR_SETINVALID
Parameter set is invalid
(7)
0x80
0x41
PAR_SETINCONSIST
Parameter set is not consistent (7)
0x81
0x82
APP_DEVNOTRDY
Application is not available
(4)
0x81 0x00
UNSPECIFIC
Manufacturer specific
(2)
0x80
0x01 - 0xFF VENDOR_SPECIFIC
Manufacturer specific
(2)
* Explanation of "Possible causes" column
(1) Contact
WAGO
Support.
(2) Contact the device manufacturer
(3) User error, IOL index/subindex is not supported by the device
(4) Contact the device manufacture if the error message appears again.
(5) Contact WAGO Support if the error message appears again.
(6) User error, select value range according to device documentation
(7) User error, select parameter set according to device documentation