WAGO-I/O-SYSTEM 750 XTR
Commissioning 89
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
The following step is included:
•
Enable DHCP
•
Assigning the IP address permanently by option “use IP from EEPROM“
8.2.2.1 Enable DHCP
Pos: 67.18.3 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbusknoten in Betri eb nehmen/Hinweis: F ür akti ve Softwar e-Konfig urati on, Adr esswahlschalter auf 255 stellen! (DHCP) @ 5\mod_1244202728786_21.docx @ 35010 @ @ 1
Set the address selection switch to 255 for assigning the IP address via
DHCP!
Set the address selection switch to 255 to disable the DIP switch and to enable
DHCP.
Restart the fieldbus node after adjusting the address selection switch to apply the
configuration changes.
Pos: 67.18.4 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbusknoten in Betri eb nehmen/U ntergruppen/Alternati v kann DHCP auch über WBM o. „ WAGO Ethernet Setti ngs"akti vi ert werden ( mit Adr wahlschalter) @ 22\mod_1431506854802_21.docx @ 182108 @ @ 1
Alternatively, DHCP will be enabled via the WBM or via “WAGO Ethernet
Settings“.
Pos: 67.18.5 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbusknoten in Betri eb nehmen/DHC P muss akti vi ert sein, Automatische IP-Vergabe durch DHCP @ 5\mod_1244202995679_21.docx @ 35014 @ @ 1
DHCP must be enabled on the Web pages or in “WAGO Ethernet Settings”!
Note if an access to the internal Web pages of WBM is already possible via an IP
address, you enable DHCP on the "Port" HTML page of the WBM, so is assigned
via DHCP a new IP address. DHCP is not enabled by default when delivered.
In other case you can also enable DHCP via “WAGO Ethernet Settings” in the
Network
tab.
An IP address is automatically assigned after restarting the fieldbus node.
Pos: 67.18.6 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbusknoten in Betri eb nehmen/Hinweis: Weitere Informati onen zum Auslesen der IP-Adresse mittels „ WAGO Ethernet Setti ngs“ @ 5\mod_1244637843934_21.docx @ 35196 @ @ 1
More information about reading the IP address
You can use “WAGO Ethernet Settings”, button
[Identify]
, via Service Interface
to read the IP addresses currently assigned.
Pos: 67.18.7 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbusknoten in Betri eb nehmen/IP-Adresse dauerhaft durch Option „use IP fr om EEPR OM“ - Ü berschrift 4 @ 5\mod_1244025692102_21.docx @ 34786 @ 4 @ 1
8.2.2.2 Assigning the IP address permanently by option “use IP from
EEPROM“
Pos: 67.18.8 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbusknoten in Betri eb nehmen/Hinweis: F ür di e dauerhafte Adr essvergabe muss di e i m EEPR OM gesp. ver wend. -DHCP ( Koppler) @ 5\mod_1244626099879_21.docx @ 35150 @ @ 1
IP stored in EEPROM must be used to assign the address permanently!
To apply the new IP address permanently in the fieldbus coupler, the option ”use
IP from EEPROM“ must be selected. Thus, the IP address is automatically
entered as static address and used in the EEPROM.