WAGO WINSTA® 770
Commissioning
33
770-629/130-000 WINSTA® Sunblind Box 4 Channel
Manual
Version 1.1.1, valid from HW/FW version XXXX0201XX
7.3
Setting Bus or Central Operation
The sunblind box has an IDC connector for a jumper bridge, with which it is
possible to select whether the box should be activated via a bus signal (RS485) or
via a 24V signal (central operation).
DIP-Modul
2
4
3
2
1
ON
DIP
ON
DIP
S7
Jumper
Figure 14: IDC connector for jumper bridge
7.3.1
Bus Operation
If the jumper bridge is plugged in the viewing direction of the figure above into
the two lower pins, bus activation is selected.
Figure 15: Jumper setting for bus operation
Factory setting
This is the factory setting for the activation type.
Setting the Bus Address
For bus operation, set the bus address using switches 1 to 5 of DIP Module 1 (see
Section "Setting the Bus Address").