255.805.001
21
Date: 2021-03-12
Adjustable parameters
Menu
Description
Range
Default
MAN SPEED
Speed for manual driving
100 – 6.000
500
MAN FWD/REV
Run the motor from the menu
STOP/FWD/REV
STOP
DMX ADDR*
DMX start address
1 - 502
1
CTRL MODE
Control Mode
1/3/4/5
3
EXT MODE
Extended Mode
NONE/ACCDCC/PIDS NONE
EMG. STOP
Emergency Stop
ON/OFF
OFF
TAC RANGE
Motor range in tacho mode
0-50.000
20.000
TAC DIVIDE
Tacho divider
1 – 512
1
MOTOR ID
Calibrate the controller to your motor
ON/OFF
OFF
LIM ACTIVE
Activate limit switches
ON/OFF
OFF
LIM RESET
Limit switch to reset the position
NONE/1 - 4
NONE
RES OFFSET
Reset offset value
0 - 4000
0
SPEED MAX
Maximum speed
100 - 15.000
1.400
SP MIN FWD
Minimum speed forward
0 - 1.000
150
SP MIN REV
Minimum speed reverse
0 - 1.000
150
ACC RAMP
Acceleration ramp
50 - 10.000
2500
DEC RAMP
Deceleration ramp
50 - 10.000
2500
NOM FREQ
Motor nominal frequency
50 or 60
50
PID P
PID regulator power setup
50 – 5000
1000
PID I
PID regulator integrator setup
0 - 5000
600
PID D
PID regulator Differentiate setup
0 - 5000
0
PID S
PID regulator S setup
50 - 5000
850
MAX CURRENT
Motor maximum current (ampere * 100)
550W: 56 - 560
3KW: 152 - 1520
300 (3A)
NOM CURRENT
Motor nominal current (ampere * 100)
550W: 0 - 420
3KW: 0 - 960
200 (2A)
NOM SPEED
Motor nominal speed
100 - 9999
1400
PF ANGLE
Power factor angle (cos ϕ * 100)
30 - 100
80
PRECISION
Precision
1 - 500
100
AUX. FUNC.
Auxiliary functions (reserved for future use)
OFF/RevoS
OFF
FACTORY
Restore to factory settings
-
-
*Identifies start position in the menu after power cycle.
Detailed explanation of parameters
WARNING: Using the Extended Mode and tuning of the PID controller can lead to uncontrolled
behaviour.
MAN SPEED
Speed for manual driving
Range
100 - 6.000
Sets the speed for manual driving the motor.
MANUAL FDW/REV
Manually driving the motor
Pressing the UP button makes the AC Motor Controller run forward, unless the limit switch is activated.
Pressing the DOWN button makes the AC Motor Controller run reverse, unless the limit switch is
activated. The AC Motor Controller will stop if the Emergency Switch is activated.
DMX ADDR
DMX start address
Range
1-502
DMX start address defines which DMX address the motor controller reacts on. The AC Motor Controller
uses minimum 4 DMX channels and up to 6 DMX channels, see mode descriptions.
CTRL MODE
Control Mode
Range
1/3/4
The AC Motor Controller has three different control modes.
Mode 1
The motor runs free run, without positioning.
Mode 3
Positioning mode with Tacho feedback.
Mode 4
Positioning mode with Tacho feedback and range set.
Mode 5
Revolving stage mode with tacho feedback and zero point sensor
See description from page 25.