22
Probe Wash Sched
Only appears if the probe wash mode has been selected.
Press
ENTER
to program the probe wash schedule. The display may read "Event A 12:00 20" which
indicates that the probe wash will start at noon and the pump will run for 20 seconds. Use the arrow
keys to change the time of day or the pump on-time. The maximum wash time is 99 seconds. If the
sensor needs to be cleaned more than once a day, as many as nine additional events may be accessed
by pressing
NEXT
. The time is Military time (1:00 PM = 13:00).
Press
EXIT
to go back to the Aux 1 menu level
Hold Time
Only appears if the probe wash mode has been selected.
Use the arrow keys to select the time delay in seconds between the probe wash ending and control
beginning again. The hold time can be programmed for a maximum of 99 seconds.
HOA
Use the Left and Right arrows to move between Hand, Off and Auto. In Hand (Manual) mode, the
output will be turned on immediately for a maximum of 10 minutes. In the Off mode, the output will
be turned off indefinitely. In the Auto mode, the output turns on and off in response to changes in the
process value relative to the set point. The letter inside the block on the status screen indicates which
mode the output is in.