INSTALLER MENU FUNCTIONS
Table 5. SmartDC Controller - Installer Menu Functions
Table 5. SmartDC Controller - Installer Menu Functions
Ref.
No�
Installer Menu
Setting Options
(
Bold
= Factory Settings)
Menu Tasks and Explanations
Associated
DC Controller
Connections
Display
14
FO 0 (OFF)
FIRE DEPT OPEN
0 = disabled
1 = enabled
Enables Fire Department Open input. When
set to 1, signal received through this input
overrides all photoelectric eyes and edge
sensors and opens the gate. Pressing the
RESET button (or the OPEN push-button) is
required before the gate can be closed.
+24V DC
EMERG OPEN
15
SE 2
IES SENSITIVITY
0 = maximum sensitivity
2 = default setting
9 = least sensitivity
Adjusts sensitivity of the internal inherent
entrapment sensor (IES). Available settings
are 0 to 9 with 9 being the least sensitive.
Wallace Perimeter Security strongly
recommends that you avoid setting the IES
sensitivity higher than 6.
Note: Before changing IES sensitivity, make
sure that the gate rolls smoothly without
obstruction. Fix any issues with gate
hardware.
See Note.
16
SS 0 (OFF)
IES STOP ONLY
0 = stop, reverse for 2s
1 = stop only
In a Usage Class 4 environment, the operator
can be set to stop the gate and not reverse
gate travel after an IES trip.
(N/A)
17
LC 0 (0.0 SECS)
LEAF DELAY CLOSE
0 = no delay
1 through 20 in ½
second increments
For example:
1 = ½ second
10 = 5 seconds
20 = 10 seconds
Only appears if the gate operator is set up as
a Primary or a Secondary. Available settings
are 1 through 20. Each increment adds ½
second time delay following a command to
close before the operator begins closing.
Provides up to a 10 second time delay.
DUAL GATE
inputs on both
operators.
18
LO 0 (0.0 SECS)
LEAF DELAY OPEN
0 = no delay
1 through 20 in ½
second increments
For example:
1 = ½ second
10 = 5 seconds
20 = 10 seconds
Only appears if the gate operator is set up as
a Primary or a Secondary. Available settings
are 1 to 20. Each increment adds ½ second
time delay following a command to open
before the operator activates. Provides up to
a 10 second time delay.
DUAL GATE
inputs on both
operators.
Summary of Contents for FOLDSMART
Page 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 FOLDSMART GATE INSTALLATION ...
Page 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 FOLDSMART GATE INSTALLATION ...
Page 146: ......
Page 147: ...FoldSmart XT Drawings Generic Site Layout and Options ...
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 160: ......