FoldSmart™ Installation and Maintenance Manual
Revision 1 - MAY 2023
79
INSTALLER MENU FUNCTIONS
Table 5. SmartDC Controller - Installer Menu Functions
Table 5. SmartDC Controller - Installer Menu Functions
Ref.
No�
Installer Menu
Setting Options
(
Bold
= Factory Settings)
Menu Tasks and Explanations
Associated
DC Controller
Connections
Display
19
RT 0 (30 SECS)
MAXIMUM RUN TIMER
0 = 30 Seconds max run
1 = 300 Seconds max
run
Assigns a motor run time of 30 or 300
seconds. If the gate opening or closure takes
longer than 30 seconds, you’ll need to set
the run timer to 1.
(N/A)
20
EC 0 (STOP ONLY)
EYE CLOSE LOGIC
0 = Close eye stops only
1 = 2s reverse to open
2 = Full Open
The default setting is non-reversal if the
close photo eye is triggered while closing.
A setting of 1 causes the gate to reverse
toward open for two seconds if triggered
while closing. A setting of 2 reverses the
gate to full open.
Sensor
Common
Sensor Input
21
EO 0 (STOP ONLY)
EYE OPEN LOGIC
0 = Open eye stops only
1 = 2s reverse to close
The default setting is non-reversal if the
open photo eye is triggered while opening.
A setting of 1 causes the gate to reverse
travel and close for two seconds if triggered
while opening.
Sensor
Common
Sensor Input
22
GC 1 NC CONTACT
GATE EDGE OUTPUT
0 = Normally Open Edge
1 = Normally Closed
This menu item only appears when UC is
set to 4. Default setting is edge sensor with
Normally Closed (NC) output. Optional
setting of 0 requires an (NO) output.
Sensor
Common
Sensor Input
23
GR 0 (FULL OPEN)
GATE EDGE LOGIC
0 = Edge reverses full
open
1 = 2s reversal only
The default setting is a full-open reversal
if the gate edge is triggered while closing.
The optional setting of 1 causes the gate
to reverse for 2 seconds if triggered while
closing.
Sensor
Common
Sensor Input
24
SR 1 REVERSE 2S
IES SENSOR LOGIC
0 = IES reverses full open
1 = 2 second reversal
only
The default setting is a two-second duration
reversal if the inherent sensor is triggered.
The optional setting of 0 will cause the gate
to reopen fully if triggered while closing.
N/A
Summary of Contents for FOLDSMART
Page 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 FOLDSMART GATE INSTALLATION ...
Page 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 FOLDSMART GATE INSTALLATION ...
Page 146: ......
Page 147: ...FoldSmart XT Drawings Generic Site Layout and Options ...
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 160: ......