VEHICLE DETECTOR AND LOOP FAULT DIAGNOSTICS
Vehicle Detector and Loop Fault Diagnostics
If HY5B vehicle detector modules are used, the SmartDC Controller has the ability to store and report
detector and loop fault information for performance diagnostics.
If the SmartDC Controller senses a loop or detector problem:
•
The LCD display flashes the name of the affected detector or error and the appropriate alert code.
•
The buzzer chirps continuously at regular intervals until the issue is resolved.
Table 12. HY5B Vehicle Detector Faults and Errors
Alert or Error
#
LCD Description
Advisory
Resolution
ALERT 7
FREQ SHIFT FAULT
HY5B vehicle detector –
Abnormal frequency change
alert.
The alert indicates an unstable loop
frequency. Check the loop and lead-in wires
for problems. Replace them, if necessary.
ALERT 8
LOOP SHORTED
HY5B vehicle detector –
Loop is shorted.
The alert indicates that the loop and lead
-
in wires are shorting out. Check the wires
for problems. Replace them, if necessary.
ALERT 9
LOOP OPEN
HY5B vehicle detector -
Disconnected loop alert.
The alert indicates the loop wires are
loose or disconnected. Check the wires for
problems. Replace them, if necessary.
ALERT 10
I²C BUSS ERROR
HY5B vehicle detector -
Communications alert.
The alert indicates the detector is not
communicating properly with the SmartDC
Controller. The alert occurs if the detector
is unplugged or the connection is unstable.
If communication is not re
-
established
within 30 seconds, the controller will reset
and the message changes to ERROR 3.
ALERT 11
DETECTOR FAULT
HY5B vehicle detector -
Malfunction alert.
The display indicates the HY5B detector
malfunction. Check detector for problems.
Replace it, if necessary.
ALERT 12
ON TOO LONG
Detector input triggered too
long –
More than five minutes.
The display indicates the HY5B detector
malfunction. The alert also works for any
input connected to the terminal strip for
standard box detectors. Check that a vehicle
is not parked on the loop. Also, determine if
the loop is stable. An unstable loop can hold
the detector in a triggered state.
Summary of Contents for FOLDSMART
Page 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 FOLDSMART GATE INSTALLATION ...
Page 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 FOLDSMART GATE INSTALLATION ...
Page 146: ......
Page 147: ...FoldSmart XT Drawings Generic Site Layout and Options ...
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 160: ......