CONNECTING HY5B VEHICLE DETECTORS
There are four vehicle detector inputs available on the SmartDC Controller as well as via the direct plug
-
in
modules. The vehicle detector input functions are as follows:
•
Free Exit Loop Detector - This opens a fully closed gate.
•
Outside Obstruction Loop Detector (Out Obs Loop) - This is for the outside reversing loop.
•
Inside Obstruction Loop Detector (In Obs Loop) - This is for the inside reversing loop.
•
Center Loop Detector - This is also known as a Shadow Loop and is used for swing gates only to
prevent a gate from starting open or closed when a vehicle is in the path of the gate.
Use of any combination of HY5B detectors
and box detectors is acceptable. On
occasion, multiple obstruction detectors
may be mandatory. For example, an area
greater than 200 square feet (19 square
meters) of loop cannot be connected to
any one detector because the sensitivity
becomes inadequate.
Connecting HY5B Vehicle Detectors
Install the HY5B Vehicle Detector modules, one at a time, according to the following procedure:
1�
Turn off both AC and DC power switches.
2�
Insert the locking end of the two white plastic standoffs into the mounting holes on the detector.
3. Plug the detector into the appropriate socket along the right edge of the SmartDC Controller board.
Be careful to align the six detector pins into the socket correctly (the screws for tightening the
terminals should face toward the board), and then snap the standoffs into the holes in the control
box.
4�
Route the loop wires through the holes provided in the control box and connect the loop leads to
the two terminals on the HY5B detector. Tighten the terminal screws securely.
5�
To enable the detector, turn on power. The detector will immediately tune if it is connected to
loops. Make sure no cars or other metal objects are over the loops.
6�
Repeat Steps 1 through 5 for each HY5B detector.
7�
If the detector module is unplugged after it is enabled, a communications alert (ALERT 10) will be
triggered; if the fault continues an error message, ERROR 3 “Detector Failed” is displayed.
Summary of Contents for FOLDSMART
Page 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 FOLDSMART GATE INSTALLATION ...
Page 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 FOLDSMART GATE INSTALLATION ...
Page 146: ......
Page 147: ...FoldSmart XT Drawings Generic Site Layout and Options ...
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 160: ......