WALLTHERM
®
produced and developed by
Walltherm
®
24/64
The combustion air mustn`t be taken through an air channel from the roof. If
necessary ask for permission from Wallnöfer and the chimney sweeper.
The lighting phase of the boiler stoves would need much more time!!
The external air channel Ø 125 mm:
The maximum length of the air channel with Ø 125 mm can be 4 m.
The air channel has to be insulated to avoid water condensation.
If you need a longer air channel please increase the diameter to Ø 150 mm.
The connection of the external air channel:
We deliver the boiler stove with a connected adapter of Ø 125 mm on the boiler stoves
backside, on the aperture on boiler stoves bottom is fixed a closed flange (cover).
If you want to connect the external air channel on the bottom, exchange the adapter on
the backside with the closed flange of the bottom.
Flap in the external air:
On the external air channel you should install a flap, so you can avoid that cold temperature
comes inside the Walltherm when it isn`t operating.
The flap can be regulated in a manual way or if you have the el. Regulation WAL03 also an
electrical flap.
The electrical air flap:
The flap should be positioned rather outside the house to avoid the channel can cooled
down. If not possible we can supply you with an electrical flap which can be fixed under or
behind the stove.
Adapter Ø 125 mm
for the external air channel
on boiler stoves backside
Closed flange (cover) on
the bottom
!
!