Thermal process safeguard valve (Emergency cooling):
For the security the Walltherm
®
boiler stove is provided with a thermal process safeguard
and it´s security heat exchanger.
In case of an interruption in the water circuit, to avoid it´s overheating, the thermal
process safeguard opens at 95°C and let pass cold water to the security heat exchanger
to cool down the heating water inside the stove.
The security heat exchanger is fixed in the upper part of the stoves heat exchanger. On
its inlet get fixed the thermal process safeguard and the cold water pipe from the water
net. On its outlet get connected the drain pipe.
Function: In case of an interruption in the water circuit (pump error) the water
temperature inside the stoves heat exchanger achieves 95°C and the thermal process
safeguard opens. Now cold water from the water net flows through the security heat
exchanger, cools down the boiler stove and the water of the heat exchanger, and flows to
the drain.
This system keeps the pressure of the heating circuit (water of the heat exchanger)
under 3 bar.
Advice: Install a non-return valve before the inlet to the thermal process
safeguard.
!Mont the thermal process safeguard in the right direction
!