23/64
4.d Combustion air
Combustion air from the room: When working, the boiler stoves takes from the room
in which he is installed a certain, small amount of air. Therefore air has to be supplied from
outside through an opening to houses that possess controlled airing and ventilation
systems.
If possible place the air inlet behind the boiler stove. The dimension of the air inlet should
be conform the laws and regulation of the installation country.
The boiler stoves air intake is on the backside!
Outside a stable grille must be fixed; on windy and stormy places should a protection
system against rain and wind should be fixed, as well.
Attention: Extractor hoods that are installed in the same room as the boiler
stove, can cause problems.
Attention: If there are other fireplaces near the Walltherm boiler stove, the
combustion air must be obtained from outside.
Danger: The norms forbid air supply from garages, storerooms where fuel and
other materials are kept and rooms where combustible
activities are practiced.
Please obey the laws and norms valid in the installation country.
Combustion air from outside:
If you would like to obtain the combustion air from outside, you can connect a
canal. Follow the right of the installation country!
On the Walltherm
®
Vajolet and Vajolet Basic we have two possibilities to connect the
channel with the external combustion air:
Backside: aperture of Ø 125 mm to connect an air channel from the backside.
Bottom: Aperture of Ø 125 mm to connect an air channel from the bottom.
Info: Close the primary air if the boiler stove isn`t operating or install the
electrical air flap controlled by the controller WAL03, in that way you can avoid
that cold air from outside cool down the boiler stove and the chimney system.
!
!
!
!
!