Malfunction Remedy

Possible causes

Remedy

Fan air output too low

Incorrect connection wiring (e.g. star instead 

of delta.e.g. star instead of delta).

Check connection wiring and correct if 

necessary.

Pressure losses too high.

Optimise duct routing.

Volume flow controllers are not or only 

partially open.

Check opening position on site.

Inlet or pressure paths blocked.

Remove blockage.

Grinding noises when 

starting or operating the 

fan

Check whether the duct connections on the 

fan are strained.

Loosen duct connections and realign.

Thermal contact/ PTC 

thermistor tripped

Direction of rotation of impeller incorrect

Change direction of rotation if 

possible. Otherwise contact Walpol.

Missing phase

If using a 3-phase motor (no EC), 

check that all 3 phases are present.

Motor overheating

Check impeller cooling (if present), 

check resistance of motor windings (if 

possible) / contact Walpol.

Capacitor (if used) not or not correctly 

connected

Connect capacitor correctly.

Motor blocked

Contact Walpol

Fan does not reach 

nominal speed

Defective motor winding

Contact Walpol

Drive motor misaligned

Contact Walpol

Control devices (if used), such as frequency 

converter or transformer, are set incorrectly.

Set control devices correctly.

Mechanical blockage

Remove blockage.

Motor does not rotate

Incorrect supply voltage

Check supply voltage, restore power 

supply.

Connection defective

Disconnect from power supply, 

correct connection according to wiring 

diagram

Temperature monitor has reacted.

Let motor cool down. Identify and 

rectify cause of fault.

Electronics/motor 

overheated

Cooling insufficient

Improve cooling.

Motor overload

Check whether the correct fan is used 

for the application.

Ambient temperature too high

Check whether the correct fan is used 

for the application.

12.3.  Maintenance

The warranty is only valid if maintenance has been carried out correctly and written proof of this has been provided.

To ensure continuous fan operation, we recommend regular maintenance intervals. These maintenance intervals are spe-

cified in the "Activities" table below. In addition, follow-up activities such as cleaning, replacement of defective components 

Summary of Contents for GB

Page 1: ...Airbox type GB GB HT GBV GBG Assembly and operating instructions Version 7 0 B04...

Page 2: ...8 7 Accessories 8 8 Installation 9 8 1 Mounting positions 10 8 2 In the W Connect system CL 12 9 CL 10 10 min 380 Pa CL 9 9 min 295Pa CL 7 7 W connect 10 8 3 Changing the discharge direction only GBV...

Page 3: ...he system relevant conditions and requirements of the system manufacturer or system builder Safety devices must not be dismantled bypassed or rendered inoperative The fan may only be used in perfect c...

Page 4: ...rotective equipment Protective equipment must be worn when carrying out any work in the vicinity of the fan Protective clothing Safety shoes Protective gloves Hard hat Safety glasses Hearing protectio...

Page 5: ...n the case of open transport ensure that no water can penetrate the motor or other sensitive components It is recommended that the fan be transported to the installation site in its original packaging...

Page 6: ...ENTRY AIR ENTRY Table 2 Dimensions Airbox GB Dimen sions mm A B C D E F G H I J K L M N O P GB 180 470 412 272 224 134 105 218 483 470 95 244 43 366 180 470 320 GB 225 522 455 301 256 147 121 251 635...

Page 7: ...in mm GBV 355 GBV 400 GBV 450 GBV 500 GBV 560 GBV A 500 670 670 670 800 800 B 500 670 670 670 800 800 C 420 590 590 590 720 720 D 378 548 548 548 676 678 E 355 404 454 504 xml ph 630Nipple dimension...

Page 8: ...blowing via contact protection grille is also possible The fan is suitable for conveying clean air The maximum permissible operating data on the type plate apply to an air density of 1 2 kg m NN and a...

Page 9: ...connectors from our accessories see chapter Accessories Prerequisites Make sure that the fan and all its components are undamaged Make sure that the information on the type plate fan and motor corres...

Page 10: ...ke sure that the drain socket is always at the lowest point of the fan so that the condensation water can drain off 8 2 In the W Connect system CL 12 9 CL 10 10 min 380 Pa CL 9 9 min 295Pa CL 7 7 W co...

Page 11: ...3 Changing the airflow direction 8 4 Assembly disassembly of impeller internal rotor motor Important Damage to the motor and the impeller The ball bearings of the motor and the balanced impeller can b...

Page 12: ...exagon socket screw 6 Impeller 7 Steel hub 8 Aluminium hub The hub is not used for the fan Hub is shown without impeller for clarity Table of tightening torques for various bushing types Socket type 1...

Page 13: ...box revision switch evenly Connect the cable end in a dry environment Install a disconnecting device permanently all pole contact opening min 3 mm in the electrical installation Protective earth cond...

Page 14: ...d by the customer in the application Never exceed the maximum impeller speed specified on the type plate of the fan Caution Damage due to non use of a sine filter Walpol always recommends an all pole...

Page 15: ...2 1 Safety instructions Troubleshooting maintenance repair may only be carried out by appropriately qualified persons for details see Table 1 Qualification The 5 safety rules must be observed see 2 3...

Page 16: ...cked Contact Walpol Fan does not reach nominal speed Defective motor winding Contact Walpol Drive motor misaligned Contact Walpol Control devices if used such as frequency converter or transformer are...

Page 17: ...X X Check that the fan and its components are used as intended X see normal operating conditions Check the current consumption and compare this with the rated data X X Check the vibration dampers if...

Page 18: ...the national regulations The unit and the transport packaging consist mainly of recyclable raw materials Dismantle the fan into its components Separate the parts according to Reusable parts Material g...

Page 19: ...1 2010 Safety of machinery Electrical equipment of machines Part 1 General requirements DIN EN 61000 6 1 2007 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for residential comm...

Page 20: ...onnected to mains without control Via contactor control 0 10 V signal EC motor Transformer Frequency converter Sine Filter Shielded cables Sealing of connection cable FESTER Clamp fit of wires Motor p...

Page 21: ...minutes For single phase fans enter in line Current L1 A pressure between suction and discharge side of the fan If a volume flow measurement is not possible the value can be calculated using the follo...

Page 22: ...in kitchen technology Observe cleaning according to VDI 2052 The intervals may be shortened in case of heavy soiling Please note If cleaning maintenance intervals are not observed warranty and guaran...

Page 23: ...23 Visual inspec tion Cleaning Maintenance Note Specialist company Stamp Date Signature...

Page 24: ...ww eu...

Reviews: