background image

 

 

1.5) DELIVERY 

 

Upon delivery of the boiler, check the nameplate to be 
sure that you have received the model with the correct 
rating and proper voltage. 
 

The following items are supplied with the unit: 
-  A pressure relief valve, adjusted to 30 psi; 
-  A drain valve; 
- A 

½

"

 NPT to 

"

 NPT reducer for the installation of an air 

purge valve; 

-  Modulating outdoor sensor. 

 

1.6) INSTALLATION

 

 

WARNING 

 

The installation of this unit must be performed by 
a qualified technician and it must conform to the 
standards and regulations in force as well as the 
Canadian Installation Code for Hydronic Heating 
Systems CSA B214-01. 

 

1.6.1)  Positioning and clearances 

 

The unit must be installed in an area that is dry, non-
corrosive, without excessive dust, well ventilated and where 
the ambient temperature does not exceed 27°C (80°F). 

 

The boiler can be installed directly on a wall, by way of the 
mounting plate, supplied with the unit.  Ensure that it is 
installed level and that the clearances indicated below are 
respected (Table 1). 

 

TABLE 1 

MINIMUM CLEARANCE 

        LOCATION 

      CLEARANCE 

Access side to elements 

   0.41 m (16") 

Other side 

15.24 cm (6") 

Above 

15.24 cm (6") 

Front 

   0.61 m (24") 

Back 0" 

 

1.7) DISTRIBUTION 

SYSTEM 

 

The proper functioning of your heating system is directly 
related to the quality of the plumbing installation.  Therefore, 
the entire installation must be performed by qualified 
technicians. 
 
See Figure 3, p. 11 for the functions of the various boiler 
connections. 
 
The heating system must be set-up to operate at a maximum 
pressure of 28 psi and the operating temperature may range 
from 32

˚

C to 99°C (90

˚

F to 210°F). 

 

Freeze protection (when required) 

 

WARNING 

 

Only propylene glycol may be used in this 
hydronic heating system, to prevent freezing. 

 

It is recommended to add a maximum of 50% of 
propylene glycol mixture to ensure proper 
operation. 

 

Do not use automotive anti-freeze, ethylene glycol 
or any undiluted anti-freeze. 

 

If the above recommendations are not followed, 
severe personal injury, death or substantial 
property and/or equipment damage can result.

 

 

All installations must include the following items: 
a.  1 pressure regulator, adjusted to 12 psi, installed 

between the boiler and the main water supply in the 
building; 

b.  1 expansion tank, pre-pressurized to 12 psi and of 

appropriate size; 

c.  1 or more automatic air purge valves; 
d.  1 or more circulating pumps of appropriate capacity. 

 

CAUTION 

To avoid water damage and/or scalding due to relief 
valve operation, a discharge line must be connected to 
the valve outlet and run to a drainage area.  The 
discharge line shall be installed in such a way that it 
will allow for the complete drainage of the valve and 
the discharge line. 

 

1.8) 

INSTALLATION OF THE BOILER 

 

At the time of installation, the following steps should be 
followed.  Refer to Figures 3 and 4, p. 11 and 12 for 
additional information. 

1. 

Choose an appropriate location.  Mount the boiler 
securely on the wall, with the help of the mounting plate.  
Ensure that it is level and that the minimum clearances 
are observed; 

2. 

Install the drain valve and the safety valve as indicated 
in Figure 3; 

3. 

An air vent can be installed on the unit.  In such case, 
use the ½" NPT to 

" NPT reducer, which is provided; 

4. 

Install the water supply and and return piping with the 1"  
NPT fitting; 

5. 

The heating supply line must include: 

a.  1 circulator along with 2 maintenance valves; 
b.  1 automatic pressure reducing valve adjusted to 

12 psi, with a shut-off valve on the return water 
line; 

c.  1 expansion tank; 
d.  1 automatic vent. 

Summary of Contents for HYDRA Series

Page 1: ...401M D HYDRA24 E2401M D HYDRA29 E2401M D 2009 08 25 X40156 Rev B Fabriqu par Corporation UTC Canada Division ICP 3400 boulevard Industriel Sherbrooke Qu bec Canada J1L 1V8 C INSTALLATEUR TECHNICIEN UT...

Page 2: ...4 INFORMATION p 8 TABLEAUX ET FIGURES TABLEAU 1 D GAGEMENT MINIMUM p 4 TABLEAU 2 POSITION DES INTERRUPTEURS DIP p 6 TABLEAU 3 SP CIFICATIONS TECHNIQUES p 10 FIGURE 1 CARTE LECTRONIQUE HYDRA p 6 FIGURE...

Page 3: ...ou dans le cas d absence de codes locaux elle doit tre conforme aux codes nationaux qui s appliquent Les renseignements contenus dans ce manuel s adressent un technicien qualifi exp riment dans ce typ...

Page 4: ...90 210 F Protection contre le gel lorsque requise MISE EN GARDE Seule une solution base de propyl ne glycol peut tre utilis e dans ce syst me de chauffage l eau afin de pr venir le gel Il est recomman...

Page 5: ...mpue pour minimiser les risques de blessures corporelles si jamais un probl me lectrique se produisait Un connecteur de mise la terre est inclus dans la bo te de contr le pour effectuer cette connexio...

Page 6: ...g e OFF ON ON Nombre d l ments Interrupteur 4 Interrupteur 5 3 OFF OFF 4 OFF ON 5 ON OFF 6 ON ON Interrupteur 6 Interrupteur 7 Interrupteur 8 Non utilis OFF OFF OFF FIGURE 1 CARTE LECTRONIQUE HYDRA A...

Page 7: ...e b timent est ligible ce tarif d lectricit et pour conna tre la fa on de faire pour l obtenir Les contr les de transfert Bi nergie BCEH sont sp cialement con us pour r pondre aux normes des fournisse...

Page 8: ...pus s accumuler au fond de la chaudi re et recouvrir les l ments chauffants Proc dure 1 Laisser refroidir la chaudi re 2 Fermer les valves d entretien qui sont install s la sortie et l entr e de la c...

Page 9: ...HIQUES 1 ET 2 Ajustement du potentiom tre Tpot 210 F Selon le graphique 1 la temp rature de l eau variera entre 210 F Tmax eau et 170 F Tmin eau Si la temp rature ext rieure est plus grande ou gale 10...

Page 10: ...ation Amp 38 62 75 83 100 120 Amp rage du circuit dimensionnement du conducteur 1 48 78 94 104 125 150 Disjoncteur fusible maximum recommand Amp 1 50 80 100 125 125 150 Alimentation Retour D bit d eau...

Page 11: ...FIGURE 3 Identification des composantes 11...

Page 12: ...FIGURE 4 Sch ma type d une installation une zone 12...

Page 13: ...FIGURE 5 Diagramme lectrique 13...

Page 14: ...FIGURE 6 Diagramme en chelle 14...

Page 15: ...FIGURE 7 Sch ma type d une installation Bi nergie sans valve 3 voies 15...

Page 16: ...FIGURE 8 Sch ma type d une installation Bi nergie avec valve 3 voies 16...

Page 17: ...17 COMPOSANTES ET PI CES DE REMPLACEMENT...

Page 18: ...LISTE DE PI CES HYDRA B50080 Rev B 18...

Page 19: ...10 L MENT EAU 240V 5KW 14 L99H012 L MENT EAU 240V 3KW 15 L99H011 L MENT EAU 240V 4KW 16 A20015 SONDE EXT RIEUR 12 C 17 B20179 01 ASSEMBLAGE SOUTIEN ARRI RE 18 B02293 24 ISOLATION 19 L02G001 PORTE FUSI...

Page 20: ...RA20 E2401M D HYDRA24 E2401M D HYDRA29 E2401M D 2009 08 25 X40156 Rev B Manufactured by UTC Canada Corporation ICP Division 3400 Industrial Boulevard Sherbrooke Quebec Canada J1L 1V8 C INSTALLER SERVI...

Page 21: ...8 4 INFORMATION p 8 TABLES AND FIGURES TABLE 1 MINIMUM CLEARANCE p 4 TABLE 2 DIP SWITCHES POSITION p 6 TABLE 3 TECHNICAL SPECIFICATIONS p 10 FIGURE 1 HYDRA ELECTRONIC BOARD p 6 FIGURE 2 BOILER WATER...

Page 22: ...information contained in this manual is intended for use by a qualified technician familiar with safety procedures and who is equipped with the proper tools and test instruments Failure to carefully r...

Page 23: ...col may be used in this hydronic heating system to prevent freezing It is recommended to add a maximum of 50 of propylene glycol mixture to ensure proper operation Do not use automotive anti freeze et...

Page 24: ...e an uninterrupted ground to minimize the risk of bodily harm A ground terminal is supplied with the control box for that purpose In the event that wires inside the unit require replacement these must...

Page 25: ...h 3 New Hydra with immersed sensor OFF ON ON Number of elements Dip switch 4 Dip switch 5 3 OFF OFF 4 OFF ON 5 ON OFF 6 ON ON Dip switch 6 Dip switch 7 Dip switch 8 Not used OFF OFF OFF FIGURE 1 HYDRA...

Page 26: ...l heater Contact your Hydro office to find out if your property is eligible to receive this rate and how to go about obtaining it BCEH dual energy controls are specially designed to Hydro standards Th...

Page 27: ...at the bottom of the boiler and covered the heating elements Procedure 1 Let the boiler cool down 2 Close the maintenance valves which are installed at the water inlet and outlet of the boiler N B It...

Page 28: ...outdoor temperature is lower or equal to 10 C 14 F Graph 2 indicates that the boiler will maintain a water temperature of 210 F Water temperature Tmax water If outdoor temperature is between 10 C 14...

Page 29: ...N A N A N A 4 4 Consumption Amp 38 62 75 83 100 120 Minimum circuit ampacity wire sizing 1 48 78 94 104 125 150 Maximum recommended circuit breaker fuse Amp 1 50 80 100 125 125 150 Supply Return Minim...

Page 30: ...FIGURE 3 Component Identification 11...

Page 31: ...FIGURE 4 Typical Diagram of a Single Zone Installation 12...

Page 32: ...FIGURE 5 Electrical Diagram 13...

Page 33: ...FIGURE 6 Ladder Diagram 14...

Page 34: ...FIGURE 7 Typical Diagram of a Dual Energy Installation without 3 way Valve 15...

Page 35: ...FIGURE 8 Typical Diagram of a Dual Energy Installation with 3 way Valve 16...

Page 36: ...17 COMPONENTS AND REPLACEMENT PARTS...

Page 37: ...PARTS LIST HYDRA B50080 Rev B 18...

Page 38: ...R PROBE 13 L99H010 WATER ELEMENT 240V 5KW 14 L99H012 WATER ELEMENT 240V 3KW 15 L99H011 WATER ELEMENT 240V 4KW 16 A20015 OUTDOOR SENSOR 12 C 17 B20179 01 MOUNTING PLATE ASSEMBLY 18 B02293 24 INSULATION...

Reviews: