background image

 

 

4

 

 

 

2 INSTALLATION 

The unit is shipped with a burner and its controls. It requires a 
115VAC power supply to the control panel and thermostat 
hook-up as shown on the wiring diagram, one or more oil line 
connections, suitable ductwork and connection to a properly 
sized vent.  

 

All local and national code requirements governing the 
installation of oil burning equipment, wiring and the flue 
connection MUST be followed. Some of the codes that may 
apply are: 

CSA B139:

  

Installation code for oil burning equipment. 

ANSI/NFPA 31:

   Installation of oil burning equipment. 

ANSI/NFPA 90B:

 Warm air heating and air conditioning 

systems. 

ANSI/NFPA 211:

  Chimneys, Fireplaces, Vents and solid fuel 

burning appliances.

 

ANSI/NFPA 70:

   National Electrical Code.  

CSA C22.1 or CSA C22.10:

  

Canadian Electrical Code. 

Only the latest issues of these codes may be used. 

2.1 POSITIONING

 

THE

 

FURNACE 

WARNING 

 

Fire and explosion hazard. 

 

The furnace must be installed in a level position, never 
where it will slope toward the front. 

 

Do not store or use gasoline or any other flammable 
substances near the furnace. 

 

Non-observance of these instructions will potentially result 
in death, bodily injury and/or property damage. 

 

CAUTION 

This furnace is not watertight and is not designed for outdoor 
installation. It must be installed in such a manner as to protect 
its electrical components from water. Outdoor installation will 
lead to a hazardous electrical condition and to premature 
failure of the equipment. 

 

 

The minimum clearances from combustible material for 
each of the positions are specified in Table 4. 

 

If the furnace is installed in a basement or on a dirt floor, in a 
crawl space for example, it is recommended to install the unit 
on a cement base 2.5 cm to 5.0 cm (1" to 2") thick. 

 

The unit must be installed in an area where the ambient and 
return air temperatures are above 15°C (60°F). In addition, the 
furnace should be installed as closely as possible to the vent, 
so that the connections are direct and kept to a minimum. The 
heater should also be located close to the centre of the air 
distribution system. 

 

2.1.1 

Installation in an enclosure 

The unit can be installed in an enclosure such as a closet. 
However, 2 ventilation openings are required for 
combustion air. The openings should be located in front of 
the furnace approximately 15 cm (6") above the floor and 
15 cm (6") below the ceiling. Figure 1 indicates the 
minimum dimensions required and the location of the 
openings.  

Figure 1 

Location and dimensions of 

ventilation air openings in a closet door  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

2.2 ELECTRICAL

 

SYSTEM 

CAUTION 

The exterior of the unit must have an uninterrupted ground 
to minimize the risk of bodily harm, if ever an electrical 
problem develops. A green ground screw is supplied with 
the control box for that purpose.

  

 

The appliance must be installed in accordance with the 
current ANSI/NFPA 70 National Electrical Code, CSA 
C22.1 Canadian Electrical Code Part 1 and/or local codes. 

 

The control system depends on the correct polarity of the 
power supply. Connect “HOT” wire (H) and “NEUTRAL” 
wire (N) as shown in Figures 3 and 4, p. 17 and 18. 

 

A separate line voltage supply should be used, with fused 
disconnect switch or circuit breaker, between the main 
power panel and the unit. 

 

Only copper wire may be used for the 115V circuit on this 
unit. If wires need to be changed, the replacements must 
have the same temperature resistance as the originals. 
 

2.3  INSTALLATION OF THE THERMOSTAT 

A thermostat must be installed to control the temperature 
of the area to be heated. Follow the instructions supplied 
with the thermostat. Also refer to the wiring diagrams 
provided with the heating/air conditioning unit. The 
connections must be made as indicated on the following 
diagrams and the wiring diagrams, p. 17 and 18. 
 

 

Thermostat Wiring 

Summary of Contents for OLR112A16A

Page 1: ...ILISER LES RENSEIGNEMENTS DANS CE MANUEL POUR L INSTALLATION ENTRETIEN DE L APPAREIL ET GARDER LE DOCUMENT PR S DE L UNIT POUR R F RENCES ULT RIEURES PROPRI TAIRE S V P GARDER CE MANUEL PR S DE L UNIT...

Page 2: ...MISE EN MARCHE 10 3 2 S QUENCE DE FONCTIONNEMENT EN MODE CHAUFFAGE AU MAZOUT 10 3 3 V RIFICATIONS ET AJUSTEMENTS 11 4 ENTRETIEN 12 4 1 NETTOYAGE DE L CHANGEUR DE CHALEUR 12 4 2 NETTOYAGE DU DISPOSITI...

Page 3: ...e iv Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service prendre en note les renseignements sur la page 14 de ce manuel pour...

Page 4: ...it Seule l dition la plus r cente des codes doit tre utilis e 2 1 EMPLACEMENT MISE EN GARDE Risque d incendie ou d explosion L appareil doit tre install au niveau Ne jamais installer avec une inclinai...

Page 5: ...ircuit devrait tre utilis entre le panneau lectrique principal et l unit Utiliser uniquement du fil de cuivre pour du courant de 115V avec cette unit Si vous remplacez des fils d origine de l appareil...

Page 6: ...es Se r f rer au manuel d instruction et marquages du contr le du br leur pour plus de d tail concernant l ajustement du d lai post purge 2 5 VACUATION MISE EN GARDE Risque d empoisonnement par monoxy...

Page 7: ...nt n est pas conforme APPELER UN TECHNICIEN QUALIFI 2 7 APPROVISIONNEMENT EN AIR DE COMBUSTION ET VENTILATION MISE EN GARDE Risque d empoisonnement par monoxyde de carbone R f rer aux codes d installa...

Page 8: ...raccordement au br leur Le conduit de mazout doit tre prot g pour viter un dommage celui ci Les installations ayant un r servoir de mazout situ sous le niveau du br leur doivent utiliser une ligne de...

Page 9: ...ventilateur Carte 1158 2 11 AJUSTEMENT DES D BITS D AIR DE VENTILATION MOTEUR VITESSE VARIABLE ECM Sur les unit s quip s d un moteur de ventilateur vitesse variable de type ECM il faut v rifier que l...

Page 10: ...fournaise et de la thermopompe Il pr vient aussi la transition directe du mode de chauffage thermopompe au mode de chauffage au mazout R f rer aux instructions du thermostat ou du contr le pour un bra...

Page 11: ...n 18 pouces de la bride d vacuation de la fournaise Pour les installations avec une vacuation murale utiliser l orifice pr vu cet effet 2 Suite un d part froid laisser fonctionner l unit environ 5 min...

Page 12: ...s de mazout accumul des vapeurs de mazout ou que la chambre combustion est tr s chaude 4 ENTRETIEN MISE EN GARDE Risque de d charge lectrique Avant d effectuer des travaux d entretien FERMER l aliment...

Page 13: ...r thermique endommag doit tre remplac 6 Nettoyer et enlever toute accumulation de salet ou obstruction de l int rieur du tube de transfert de chaleur 7 Remonter verrouiller et fixer le bo tier de comm...

Page 14: ...se du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature...

Page 15: ...IELLO MOD LE 40 BF5 vacuation directe DV Longueur d insertion du tube du br leur pouces Gicleur Delavan 0 60 70A 0 70 70A 0 60 70A 0 70 70A Pression de la pompe minimum et maximum PSIG 130 160 130 160...

Page 16: ...rtRun D lai On Niveau PCM Temps D lai Off Niveau PCM Temps A 1 OFF 2 OFF 0 68 13 45 sec 19 60 sec 38 3 min B 1 ON 2 OFF 0 80 13 45 sec 19 30 sec 38 3 min C 1 OFF 2 ON All 13 45 sec 100 0 sec 100 2 min...

Page 17: ...N STATIQUE EXTERNE AVEC FILTRE AIR EMPLACEMENT APPLICATION D GAGEMENTS mat riaux combustibles ACC S RECOMMAND POUR L ENTRETIEN FOURNAISE 2 54 cm 1 0 6 m 24 PL NUM D ALIMENTATION JUSQU 1 8m 6 DE LA FOU...

Page 18: ...18 Figure 2 Dimensions de la fournaise...

Page 19: ...19 Figure 3 Diagramme lectrique Moteur 4 vitesses PSC...

Page 20: ...20 Figure 4 Diagramme lectrique Moteur vitesse variable ECM...

Page 21: ...21 COMPOSANTES ET PI CES DE REMPLACEMENT...

Page 22: ...22 LISTE DE PI CES Avec moteur 4 vitesses PSC B50093B...

Page 23: ...E DROIT 26 B03711 01 SUPPORT FILTRE ANGLE DROIT 27 B03553 ESPACEUR DE BOITE ELECTRIQUE 28 B03549 BOITE ELECTRIQUE 29 R02R003 CONTR LE HAUTE LIMITE L195 30 1 75 po 30 B03550 COUVERCLE BOITE ELECTRIQUE...

Page 24: ...24 LISTE DE PI CES Avec moteur vitesse variable ECM B50094B...

Page 25: ...14 01 ISOLATION PANNEAU DE COTE DROIT 26 B03711 01 SUPPORT FILTRE ANGLE DROIT 27 B03553 ESPACEUR DE BOITE ELECTRIQUE 28 B03534 BOITE ELECTRIQUE 29 R02R003 CONTR LE HAUTE LIMITE L95 30F 1 75 po 30 B035...

Page 26: ...CIAN USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FU...

Page 27: ...OPERATION 9 3 1 START UP 9 3 2 OPERATING SEQUENCE OIL HEATING MODE 9 3 3 CHECKS AND ADJUSTMENTS 9 4 MAINTENANCE 11 4 1 CLEANING THE HEAT EXCHANGER 11 4 2 CLEANING THE BLOCKED VENT SHUT OFF DEVICE BVS...

Page 28: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 29: ...ea where the ambient and return air temperatures are above 15 C 60 F In addition the furnace should be installed as closely as possible to the vent so that the connections are direct and kept to a min...

Page 30: ...able 1 and based on a pump pressure of 100 psi Always select nozzle sizes by working back from the desired flow rate at operating pressure and not the nozzle marking 2 4 2 Air and Turbulator Settings...

Page 31: ...l switch will shut down the oil burner The device will then need to be re armed MANUALLY Refer to the detailed instructions and wiring diagrams supplied with the BVSO for the installation and wiring p...

Page 32: ...s Ensure that the tank is full of clean oil Use No 1 or No 2 Heating Oil ASTM D396 U S or in Canada use No 1 or No 2 Furnace Oil A manual shut off valve and an oil filter shall be installed in sequenc...

Page 33: ...Positions 1 2 POSITION Output Tons OFF OFF A 4 0 ON OFF B 3 5 OFF ON C 3 0 ON ON D 2 5 CFM ADJUSTMENTS ALL MODES SW3 ADJ Adjustment DIP Switch Positions 1 2 POSITION CFM HTG increase or decrease CFM...

Page 34: ...the unit turn the main electrical switch on 3 2 OPERATING SEQUENCE OIL HEATING MODE 1 The W R contact closes 2 The burner motor starts up to pre purge the combustion chamber for a period of 10 to 15 s...

Page 35: ...xcessive combustion air due to the air band being too wide open or a lack of flue draft chimney effect or some other blockage such as soot in the secondary section of the heat exchanger or the use of...

Page 36: ...bling the unit the heat exchanger and combustion chamber should be inspected to determine if replacement is required 9 After the cleaning replace the heat exchanger baffles flue collar plate and oil b...

Page 37: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Page 38: ...vent DV Burner tube insertion length inches Nozzle Delavan 0 60 70A 0 70 70A 0 60 70A 0 70 70A Minimum and Maximum pump pressure PSIG 130 to 160 130 to 160 130 to 160 130 to 160 Combustion air adjust...

Page 39: ...e ShortRun On Delay CFM Level Time Off Delay CFM Level Time A 1 OFF 2 OFF 0 68 13 45 sec 19 60 sec 38 3 min B 1 ON 2 OFF 0 80 13 45 sec 19 30 sec 38 3 min C 1 OFF 2 ON All 13 45 sec 100 0 sec 100 2 mi...

Page 40: ...890 860 830 BLOWER SPEED EXTERNAL STATIC PRESSURE WITH AIR FILTER LOCATION CLEARANCES combustible materials RECOMMANDED ACCESS FOR SERVICE FURNACE 2 54 cm 1 0 6 m 24 SUPPLY PLENUM WITHIN 6 FEET OF FUR...

Page 41: ...16 Figure 2 Furnace dimensions...

Page 42: ...17 Figure 3 Wiring Diagram 4 Speed Motor PSC...

Page 43: ...18 Figure 4 Wiring Diagram Variable Speed Motor ECM...

Page 44: ...19 COMPONENTS AND REPLACEMENT PARTS...

Page 45: ...20 PARTS LIST With 4 speed motor PSC B50093B...

Page 46: ...HT SIDE PANEL INSULATION 26 B03711 01 RIGHT ANGLE FILTER RACK 27 B03553 ELECTRICAL BOX SPACER 28 B03549 ELECTRICAL BOX 29 R02R003 HIGH LIMIT L195 30F 1 75 in 30 B03550 ELECTRICAL BOX COVER Panel only...

Page 47: ...22 PARTS LIST With variable speed motor ECM B50094B...

Page 48: ...and baffle included 25 B03714 01 RIGHT SIDE PANEL INSULATION 26 B03711 01 RIGHT ANGLE FILTER RACK 27 B03553 ELECTRICAL BOX SPACER 28 B03534 ELECTRICAL BOX 29 R02R003 HIGH LIMIT L195 30F 1 75 in 30 B03...

Reviews: