Page | 11
OPERATING THE GENERATOR
Before starting the engine:
Check engine oil level
Check engine coolant level
Confirm that sufficient fuel is in the fuel tank
Confirm that the Emergency Stop Button is not depressed (rotate clockwise to release)
Confirm that the Battery Disconnect is closed
Confirm that the Main Circuit Breaker is in the OFF position.
Starting the engine in Manual Mode:
All engine starting controls are located at the operator end of the generator.
Switch the Controller Power toggle to the ON position.
Review and resolve any notices or alarms from the Controller.
Press and release the Manual Mode button on the Controller.
Press and release the Start Engine button on the Controller. The engine will start after a few
seconds of glow plug engagement.
Allow the engine to warm up for a few minutes before applying load.
Stopping the engine in Manual Mode:
Emergency shutdown - Press the Emergency Stop Button (located beside the electrical connection
panel) to immediately stop the engine in the event of an emergency.
DO NOT use the Emergency Stop Button for normal shutdown.
Normal shutdown - Press and release the Stop/Reset button on the Controller.
Disconnect (Open) the Generator from the Load in Manual Mode:
Turn off loads as appropriate depending on how the generator is being used.
Switch the Main Circuit Breaker open.