installation, servicing and user instructions manual | GB + IE
15
3.4.6 Horizontal Wall Vent Termination type C11
Flue sizing:
Danta 500:
Ø100/150 Connector on Appliance. Ø100/150 to be used Throughout.
Flue Terminal:
Ø100/150 Part No. INK.4330
Danta 800, 1100, 1400 & Koto: Ø130/200 Connector on Appliance. Ø130/200 to be used Throughout.
Flue Terminal:
Ø130/200 Part No. INK.4430
Vertical Flue
Rise (V) in
metres
Maximum
Horizontal Flue Run
(H) in metres Danta
500
Maximum
Horizontal Flue Run
(H) in metres Danta
800
Maximum
Horizontal Flue Run
(H) in metres Danta
1100 & Koto
Maximum
Horizontal Flue Run
(H) in metres Danta
1400
0,5
1
2
1,75
1,5
1
2,5
3,5
3
2,5
1,5
3,5
5
4,25
3,5
2
4
6
5,5
4,5
2,5
4,5
6
6
5,5
3
5
6
6
3,5
5,5
6
4
6
4,5
6
Minimum Vertical Flue Height: 0.5m
Flue Restrictors to be fitted:
Ø100/150, Vertical Rise < 1m, No Restrictor.
Ø100/150, Vertical Rise > 1m, 35mm Restrictor.
Ø130/200, Vertical Rise, 1m, No Restrictor.
Ø130/200, Vertical Rise 1-2m, 35mm Restrictor.
Ø130/200, Vertical Rise > 2m, 60mm Restrictor.