Data transfer per TCP/IP sockets
Subject to error and alteration
Serial addressing (Parameter
Client: „C“+Addr
) also makes chan-
ging connections between multiple Com-Server ports possible.
In this case the addressing must be generated by the serial
devices.
Example 1:
A control program polls a measuring device; the
measuring device is passive.
A
B
serial connection
Intranet /
Internet
Configuration menu:
r
TCP/IP Mode
r
TCP-Client
Com-Server A
- Server Port: 8000
- Server IP:
IP address Com-Server B
- Client "C"+Addr: deactive
Com-Server B
- Server Port: 0000
- Server IP: 0.0.0.0
- Client "C"+Addr: deactive
Example 2:
A control program polls a measuring device; the
measuring devicve can actively send data to the control pro-
gram.
A
B
serial connection
Intranet /
Internet
Configuration menu:
r
TCP/IP Mode
r
TCP-Client
Com-Server A
- Server Port: 8000
- Server IP:
IP address Com-Server B
- Client "C"+Addr: deactive
Com-Server B
- Server Port: 8000
- Server IP:
IP address Com-Server A
- Client "C"+Addr: deactive