1) , the status on light’s indication
PWR: green, normal work light.
ALM: red, failure light, the motor with phase short-circuit, overvoltage and under-voltage
protection.
2) Troubles

Alarm indicator

Reasons

Measures

LED off turn

Wrong connection for

power

Check wiring of power

Low-voltages for power

Enlarge voltage of

power

Motor doesn’t run,

without holding

torque

Wrong connection of

stepper motor

Correct its wiring

RESET signal

is effective when

offline

Make RESET

ineffective

Motor doesn’t run,

but maintains holding

torque

Without input pulse

signal

Adjust PMW & signal

level

Motor runs wrong

direction

Wrong wires’

connection

Change connection for

any of 2 wires

Wrong input direction

signal

Change direction

setting

Motor’s holding

torque is too small

Too small relative to

current setting

Correct rated current

setting

Summary of Contents for DQ860MA

Page 1: ...gher It is widely used in middle and big size numerical control devices such as curving machine CNC machine and computer embroider machine packing machines and so on Features l High performance low pr...

Page 2: ...al PUL is the positive end of pulses input pin PUL is the negative end of pulse input pin DIR DIR DIR signal DIR is the positive end of direction input pin DIR is the negative end of direction input p...

Page 3: ...l level is active all control negative signals will be connected together to GND When low electrical level is active all control positive signals will be connected together to public port Now give two...

Page 4: ...on choice Using DIP pins to achieve this function 1 Micro step resolution is set by SW 5 6 7 8 of the DIP switch as shown in the following table SW5 O N OF F ON OF F ON OFF ON OFF ON OF F ON OFF ON OF...

Page 5: ...bits SW 1 2 3 of the DIP switch are used to set the dynamic current Select a setting Closest to your motor s required current Output current A SW1 SW2 SW3 PEAK RMS ON ON ON 2 80 2 00 OFF ON ON 3 50 2...

Page 6: ...80VDC The peak input current can not up to 6A 5 Mechanical Specification To have 20mm of space around cannot be placed next to other heating devices What s more avoid dust oil mist corrosive gas heavy...

Page 7: ...f power Motor doesn t run without holding torque Wrong connection of stepper motor Correct its wiring RESET signal is effective when offline Make RESET ineffective Motor doesn t run but maintains hold...

Page 8: ...e out mechanical failure Driver does not match with the motor Change a suitable driver 7 Driver wiring A complete stepper motor control system should contain stepper drives DC power supply and control...

Page 9: ...g Warranty Service To obtain warranty service a returned material authorization number RMA must be obtained from customer service at e mail sales wantmotor com Before returning product for service Cus...

Reviews: