890362_b•en•21.03.2011
We reserve the right to carry out improvements
34
WAREMA Quatronic dialog
®
Operating instructions
6.3.2 Ice alarm
The ice monitor combines the precipitation and temperature readings. If the
outside temperature drops below +3°C and precipitation falls onto the pre-
cipitation sensor, all sun shading products are raised.
During the UP command, the Quatronic dialog switches to the
Position
and
Cause
display. If the run time for raising the sun shading product has expired,
Ice
appears on the display for the facades with ice monitoring to indicate the
trigger, and
Menu
appears as a reference to the "Ice menu".
Position: Menu Menu Upper Upper
Cause: Ice Ice Rain Sun
On the facades with ice monitoring, all comfort functions are blocked during
an ice alarm.
However, you can use the
/
buttons to open the "Ice menu" on these
facades:
ICE ALERT: Reset the ice alert until
next ice alert trigger? YES NO
WARAIAG
You now have the option of disabling the ice warning until the next
ice alarm occurs at your own risk, and you can re-enable the comfort
functions and manual operation. It is important that you first make sure
that none of the sun shading products are already frozen. If a product is
frozen, do not start a manual operation.
The following confirmation prompt appears after pressing
Yes
:
ATTENTION! Resetting ice alert enables
local operation at MCU and comfort...-->
... functions! Reset ice alert?
YES NO
To disable the ice monitor, press the
Yes
button.
The following menu is displayed:
Reset active YES NO YES YES
ice alert? F 1 F 2 F 3 F 4
Safety functions
Ice monitor