7.1.1 Setting the sun control
The following parameters can be set for the sun control:
Lim.
= "Up" sun limit value (1 - 99 kLx)
Lim.
= "Down" sun limit value (1 - 99 kLx)
Dely
= On delay (0 - 99 min)
Dely
= Off delay (0 - 99 min)
Alloc
= Photo sensor allocation (1, 2, 3, 4, 1-4)
Keep the
disp/prog
button pressed for approx. 5 seconds.
Wind speed: 8m/s 8m/s 8m/s 8m/s
Time: 10:26:47 Wednesday, 20.11.2008
The selection menu is displayed:
Select the Wind RunT Timer Sun
settings: Rain Temp Product -->
Press the
button above the word
Sun
.
The
Sun
menu is displayed.
Sun Lim.
Dely
setting: Lim.
Dely Alloc
Select the desired parameter by pressing the
or
button.
Example
UP sun limit value (
lim.
)
In this menu, you can change the settings for each facade (
F1
-
F4
) using the
/
buttons.
Limit UP
: 30kLx 30kLx 30kLx OFF
CH1 CH2 CH3 CH4
Leave the menu after completing the entries using the
disp/prog
button.
This saves the changes you made.
omfort functions
Sun control