WAREMA Quatronic dialog
®
Operating instructions
7.3.4 Outside settings up/down,
inside settings up/down
The effects of the settings are addressed below in more detail.
A temperature control command can have a variety of effects, which you can
select in the
Temp
menu.
Limit values:
Normally, the DOWN limit value (
Out
or
In
) must be larger than the UP
limit value (
Out
or
In
): If the temperature reading exceeds the DOWN limit
value, the DOWN move command is triggered or the sun control is switched
on.
If the temperature reading drops below the UP limit value, an UP move com-
mand is triggered or the sun control is switched off and an UP move com-
mand is triggered.
NOTE
The temperature control has no delays since temperatures change slowly.
7.3.5 InOM, OutOM, Alloc
settings
Operating modes:
If the inside/outside temperature control is to execute a move command, se-
lect the
Move
setting in the
InOM
,
OutOM
menus.
If the inside/outside temperature control is to enable the sun control, select
the
Sun
setting in the
InOM
,
OutOM
menus.
Allocation:
One outside temperature sensor and/or up to 4 inside temperature sensors
can be connected to the Quatronic dialog. These sensors are allocated to
the 4 facades in the
Alloc
menu.
omfort functions
Temperature control