background image

5

1.800.556.0595

 

for assistance 

Warmsource-N/P Preparation

INSTALL LOCATION

Before installing Warmsource-N/P, it’s important  
to consider its location. Like all gas-fired boilers,  
this appliance does make a small amount of noise 
which may be disruptive if installed near a bedroom 
or common living space. Garages and basements  
are the better choice. Installation of a drain pan is 
highly recommended.

INSTALLING DISTRIBUTION LINES

After the tubing and manifolds, install the manifold 
distribution lines. Sizing, layout and length of the 
piping can be found in the WCS Design Drawings.

 

f

Pressure test all distribution lines for 15 minutes  
at 100 PSI (International Mechanical Code,  
section 1208.1)

MINIMUM CLEARANCES

This illustration shows the recommended minimum 
dimensions for the Warmsource-N/P mechanical 
area. This image also depicts the space necessary for 
piping and mechanical components. The minimum 
depth is 40" for access and serviceability.

18"

46"

32"

3+"

86"

12"

Install the Warmboard-supplied ball valves and 
hose bibs and shown in our Design Drawings  
for the proper filling and purging of air from  
the system.
Pre-plumb boiler components prior to drywall. 
Reference page 6 of this guide and/or the  
HTP Manual.

Warmsource-N/P cabinet dimensions: 
17.5W x 56H x 15.5D
View the boiler page in the WCS Design 
Drawings to see how the manifold distribution 
lines should be plumbed, and get a better idea 
of labor costs.

Summary of Contents for Warmsource-N

Page 1: ...1 1 800 556 0595 for assistance FOR USE WITH Warmsource N natural gas boiler Warmsource P propane gas boiler Warmboard Comfort System INSTALLATION GUIDE 1021...

Page 2: ...e exhaust gas vent is required 7 The constant pressure circulation pump s inside Warmsource N P adjust flow rates depending on the needs of each zone 8 Once system plumbing is complete test the system...

Page 3: ...and WCS f Foundation and joist f Install Warmboard S f Install tubing some loops before walls f Frame walls roof sheeting f Install tubing manifolds some loops f Install all 120 volt electrical boxes...

Page 4: ...red by code in many jurisdictions it prevents water in the closed loop system from mixing with the domestic water f Air purging valves a 1 1 4 combo ball valve hose bib along with several smaller valv...

Page 5: ...ibution lines for 15 minutes at 100 PSI International Mechanical Code section 1208 1 MINIMUM CLEARANCES This illustration shows the recommended minimum dimensions for the Warmsource N P mechanical are...

Page 6: ...301 2 56 11 4 Brass Union supply 11 4 Brass Union return 3 Air Intake T P Relief Valve 3 Exhaust 53 4 57 8 6 3 4 Gas line left side preferred right side OK Condensation Discharge Line 361 2 171 2 21 2...

Page 7: ...cket the unit weighs 150lbs and requires two individuals to move safely CONNECTIONS f Connect the PVC intake and exhaust lines gas line condensation discharge line and T P relief discharge line per th...

Page 8: ...ng the system with water for 10 15 minutes until air cannot be seen or heard escaping the hose f Close the fast fill lever then slowly close hose bib A f Ensure the pressure gauge located inside Warms...

Page 9: ...p 3 Plug Warmsource N P into the 120 volt outlet and confirm the system is ON using the rocker switch and power button circled in the photo to the right Warmsource N P will reach the target temperatur...

Page 10: ...sign Drawings CONTROLS Warmboard Controls consist of the following f 120 volt thermostats one per heating zone f 120 volt Manifold Controller one per manifold f 24 volt solenoid valve loop actuators o...

Page 11: ...inaccurately If there are any discrepancies regarding the thermostat or zoning contact us immediately f Remove the appropriate thermostat from the box f Grip the face of the thermostat on the sides w...

Page 12: ...rminal connection AC1 Fan on the Smart Reset Controller SRC f Connect the wires from the AC unit to the terminal block accordingly RC 24v power red wire Y Cooling Call yellow wire G Fan green wire f T...

Page 13: ...inutes the green lights will turn blue indicating that the actuators have opened and water is flowing to the zone f If something does not appear to be working properly consult your Warmboard Engineere...

Page 14: ...E ARE EXPRESSLY EXCLUDED FAILURE TO INSTALL WARMBOARD PRODUCTS ACCORDING TO MANUFACTURER S INSTRUCTIONS WILL VOID ALL APPLICABLE WARRANTIES IT IS EXPRESSLY UNDERSTOOD THAT WARMBOARD IS NOT RESPONSIBLE...

Reviews: