11.8 Servicing
11.8.1 General Requirements
The appliance must be serviced annually by a Warmflow or OFTEC registered service
technician in accordance with the recommendations laid out in OFTEC’s Technical Book 2:
‘Domestic & Light Commercial Servicing and Commissioning – Requirements for Oil Fired
Systems – Pressure Jet Appliances’.
Additionally, when servicing, special attention
MUST
be paid to the condition of the oil nozzle,
flexible oil line, fuel filter, door insulation, sealing rope, expansion vessel (inc. pre-charge) and
the secondary heat exchanger door seal. If found to be defective, they
MUST
be replaced.
If fitted, the magnetic filter must be serviced per the manufacturer’s instructions.
Flexible oil lines must be replaced if out of their guarantee period. If doubt exists as to the
guarantee period expiry date of the flexible oil lines, or if their integrity is uncertain, they
MUST
be replaced as part of the service.
The operation of boiler appliance safety controls and devices such as high limit thermostats,
pressure relief valves and fire valves
MUST
be assessed. If found to be defective, they
MUST
be replaced.
N.B.: Where they exist, wheel-head fire valves
MUST
be replaced with a remote acting type.
The system corrosion inhibitor concentration must be checked during annual servicing (instant
on-site test kits are available from inhibitor manufacturers) and additional inhibitor
MUST
be
added if the system is found to be under-dosed. Refer to the inhibitor manufacturer for further
guidance.
Note: All product warranties will be invalidated if the appliance is not serviced annually
by a Warmflow or OFTEC trained and registered technician. Details of the servicing
conducted must be recorded in the OFTEC Boiler Passport.
9
Perfector 9 Side:Front
Summary of Contents for Agentis Series
Page 2: ......
Page 30: ...Page 29 4 5 Components 4 5 1 B Series Boilerhouse Casing Key Components...
Page 31: ...Page 30 4 5 2 I Series Internal Casing 21 26 33 Models 44 Models...
Page 32: ...Page 31 4 5 3 I Series Internal Key Components 21 26 33 Models 44 Models...
Page 33: ...Page 32 4 5 4 I Series Internal Pump Group 21 26 33 Models 44 Models...
Page 35: ...Page 34 4 5 7 E Series External Casing 21 26 33 Models 44 Models...
Page 36: ...Page 35 4 5 8 E Series External Key Components 21 26 33 Models 44 Models...
Page 37: ...Page 36 4 5 9 E Series External Pump Group 21 26 33 Models 44 Models...
Page 39: ...Page 38 4 5 12 Combination Boiler Pipe Layout...
Page 41: ...Page 40 5 1 2 I Series Internal I21 I26 I33 5 1 3 I Series Internal I44...
Page 43: ...Page 42 5 1 6 E Series External Base Tray E21 E26 E33 5 1 7 E Series External E44...
Page 45: ...Page 44 5 1 10 E Series External Combination Boiler Base Tray E21C E26C E33C...
Page 61: ...Page 60 6 3 3 External 230V Two Channel Programmer Room Thermostat Optional Outdoor sensor...
Page 62: ...Page 61 6 3 4 Internal Two Channel Programmer and Room Thermostat Optional Outdoor Sensor...
Page 73: ...Page 72 6 6 9 Honeywell Y Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Page 74: ...Page 73 6 6 10 Honeywell S Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Page 93: ...Page 92 Kabin Pak External Plume Management Kit KPMK The kit comprises...
Page 107: ...Page 106 11 4 Burner Start Up Cycle Lock out is indicated by a lamp on the control box...
Page 122: ...Page 121 14 SPARES 14 1 RDB 2 2 BX Spares...
Page 124: ...Page 123 14 2 RDB 3 2 BX Spares...
Page 134: ...Page 133 Intentionally left blank...
Page 135: ......