INSTALLATION INSTRUCTIONS
TR05A140.B1107
26
4.8.2 Horizontal coaxial balanced flue – Ø 60/100 (Kit K)
Figure 18: Ø 60/100 Horizontal Kit K
Figure 19: Ø 60/100 Horizontal Kit K dimensions
FOR CONDENSING BOILERS ONLY
Ø 60/100
MAXIMUM FLUE LENGTH = 5 m *
The flue length is the total length of the flue
excluding the first bend
.
The total length is calculated by summing
the lengths of all the straight section AND
the equivalent lengths of each bend (see
below).
Ø 80/125 x 90° bend = 0.8 m
Ø 80/125 x 45° bend = 0.5 m
* If a flue length of above 5 metres is
required, use the Ø 80/125 system.