Page 43
3.6.3 Programmer Installation
.
Disconnect electrical supply.
2.
Drop down control box front (2 screws).
3.
Secure control box to the horizontal casing bracket (2 screws) and right hand side
( screw).
4.
Connect the thermostat, circulating pump and the mains supply to the leads on the
rear of the control box.
5.
Two examples of system wiring are shown in the following sections.
6.
If fitting the programmer to a Utility model without an integral pump, disconnect the
pump plug from terminals and 2 of the programmer terminal block and from the
earth post. Remove the pump plug then wire the external plug into terminals and
2 of the programmer terminal block and the earth post, feeding the wire in through
the pump plug cable clamp.
7.
Activate battery backup on programmer by removing the plastic strip.
8.
Close the control panel cover (2 screws) and reconnect the electrical supply.
9.
Using the operating instructions located towards the back of this manual or supplied
with the programmer, set the switching times.