Figure 19
Condensed Vertical Adapter and vertical flue set installation detail
Figure 20
Hermetic and vertical flue set installation application
Implementation
L1
= 0.3 m.
L2
= 0.5 m. (45° elbow equivalent length)
L3
= 1.0 m.
L4
= 0.5 m. (45° elbow equivalent length)
L5
= 0.5 m.
L6
= 0.5 m.
L Total
= 3.3 m.
3.3 m. < Lmax = 6 m.
Correct in implementation
2.2.15. Installation at Partially Protected Exteriors
Installation Instructions: This combi can be installed in partially protected
exteriors but not fitted in places at risk of atmospheric damage – and
protected against poor weather.(rain, snow, etc.).
Frost protection:
Combi device is equipped with a system that prevents
frost by automatically activating the pump and boiler when the internal
water is lower than 5°C.
Frost protection function only depends on below given conditions:
- If the combi is correctly connected to gas and electrical sources;
- If the combi is supplied from gas and electricity sources in a fixed way;
- If the Combi is not in failure situation due to lack of ignition;
- If radiator installation pressure is full and radiator valves are open;
- Provided main components are not damaged, the combi is protected
against frost up to -5°C environment temperature.
Lowest Temperature -5°C.
In case the combi is installed in an environment
with a temperature lower than -5°C, and gas supply is interrupted or
passed into failure due to failing to make ignition, Frost Prevention System
shall not be activated and frost/failure shall occur in the device. Following
instructions should be followed for preventing the risk of frost:
- Heating circuit; anti freeze may be used with caution according to
manufacturer's instructions.
In case of having flammable walls or passages in environments with
Hermetic Flue Type, fire resistant insulation material is placed between the
wall and exhaust gas relief pipe.
Materials used for manufacturing the combi are resistant against
glycol and propylene based anti-frost liquids. Follow warnings by
supplier company instructions for safe disposal..
- If the combi is correctly connected to the electrical source;
- If the main switch is on;
Under these conditions, the combi is protected against frost up to -5°C
temperature.
Frost protection of the combi boiler is guaranteed only under these
conditions:
Damages arising from interruption of electrical power and not following
issues mentioned in previous pages regarding efficiency of Warranty.
Note: In case the combi device is installed at places with
temperature lower than 0°C (both for domestic hot water ad
radiator purposes) both radiator installation and tap water pipes
must be insulated.
2.2.16. Electrical Connections
Ensure electrical safety of combi by connecting to an effective
earthing installation that follows safety instructions in force. It is dangerous
and unacceptable to use gas and water connection pipes for earthing.
WARNING! WARMHAUS A.Ş. cannot be held responsible for any damage
or loss to individuals or property arising from failing to provide earth
connection of the combi and not being fitted by a competent
electrician or registered individual in accordance with directives and
standards in force in the country where the boiler is fitted.
Also, ensure that the electricity installation complies with the maximum
power to be supplied as indicated in technical specifications label Combi is
supplied with "X" type socketless special power supply cables.
"Warmhaus combi has an IPX5D protection level. Power supply cable
should be connected to 230 V +%10; -%15 50Hz grid with L-N poles and
relying on the earth connection, high voltage category 3rd class multiple
poled disconnected should be envisaged on the same grid. Your device