background image

19

warmhaus.com

3.2.6. Selection of On/Off/Standby and Summer/Winter Modes

ON/OFF button is not available on the combi panel. Switching on/off should 
be performed on the V automat switch connected to the combi line.

3.2.7. On/Off/Standby Positions

ON/OFF button is not available on the combi panel. Switching on/off should 
be performed on the V automat switch to be connected to the combi line.

3.2.8. Operation at Winter Position

At that position, combi operates both for heating the environment and 
providing hot tap water. Radiator temperature adjustment is made 
with (3) and (4) numbered buttons in Figure 28, Domestic Hot Water 
temperature adjustment is made with (7) and (8) numbered buttons and 
this temperature is indicated with (10) numbered indicator for Radiator and 
with (12) numbered indicator for Domestic Hot water.

Analogue manometer is located near to right-bottom side of the 
combi.  Installation pressure should be seen in this manometer 
even in the absence of electricity.

When combi is started, flame modulation symbol is seen at the middle 
section of the screen.   At that position, you can increase and decrease the 
temperature with radiator temperature  adjustment buttons (see. Figure 
28) (3) between 35 – 80 °C, screen lights when buttons are pressed and °C 
symbol flashes besides the radiator temperature value.

3.2.9. Operation at Summer Position

Combi only operates for heating the domestic hot water at that position. In 
order to switch to domestic hot water position;

When the combi is started for the first time, 
screen displays nG letter and then a number 
(for instance 24) indicating kW power of the 
device. 

Then, OFF letter is displayed,

and screen light is closed. Now, combi is at 
STANDBY position. The temperature value 
when electricity is supplied to the device 
is the temperature value of water in the 
installation.

Hold the MODE button for switching on the 
combi when letter is available on the screen.

A cycle starts on the screen.

Release the button when cycle is completed.

In some cases, combi initially gets into Radiator 
position, its symbol flashes on the left bottom 
corner of screen and tap symbol is seen at right 
bottom corner.   A digital manometer indicating 
the installation pressure is located on the lower 
middle section of the screen and also existing 
radiator installation temperature is seen on 
the screen at the same time and screen light is 
turned off.

{If you have a ground heating system, as our Authorized 
Service adjust your combi for “Low Temperature Operation”, 
maximum temperature shall be limited with the Radiator 
temperature adjustment button (3) (e.g. maximum 50 °C)}.

Domestic Hot Water Adjustment at Winter 
Position; You can adjust the hot tap water 
temperature value between 35 – 60 °C with (7) 
and (8) numbered buttons under the RESET 
button. Screen lights during temperature 
change, DHW symbol flashes besides the DHW 
temperature value. Screen light turns off after 
adjustment.

If you are starting the combi for the first time 
hold MODE button, and release the button after 
the cycle is completed on the screen, initially 
combi switches to radiator position, its symbol 
will flash on left top corner of the screen 
existing radiator installation temperature and 
screen light will turn off. 

In order to switch to tap water position, hold 
MODE button and release the button after 
completion of cycle on the screen.   At that 
position, symbol flashes at right bottom corner 
of the screen and existing domestic hot water 
temperature will be seen on the screen and 
screen light will turn off.

At that position, you can adjust the hot tap 
water temperature between 35 –60 °C with (7) 
and (8) numbered buttons below the RESET 
button.

Screen lights during temperature change, DHW 
symbol flashes besides the DHW temperature 
value.   Adjustment value is confirmed 
after screen light turned off following the 
adjustment.

Summary of Contents for LAWA 18

Page 1: ...CONVENTIONAL COMBI BOILERS INSTALLATION USER MANUAL LAWA LAWA PLUS...

Page 2: ...Lawa LawaPlus Enerwa E24 EnerwaPLUSE24...

Page 3: ...2 2 16 Installation at Partially Protected Exteriors 12 2 2 17 Electrical Connections 12 2 2 18 Optional Controls Room Thermostat External Weather Temperature Sensor and Others 13 2 3 HYDRAULIC INSTA...

Page 4: ...under any circumstances during installation use or maintenance operations and device warranty shall also be void Only the authorized Warmhaus Service is authorized to make the electrical connection o...

Page 5: ...r matches Close valves of devices operating with natural gas and your gas meter Immediately evacuate the place with gas odour Natural Gas Emergency Line from your neighbour or another suitable place D...

Page 6: ...lace Wall installation for the combi boiler should be well secured The hanger plate given as standard with the combi should be installed according to the technique to a full or semi full brick wall ac...

Page 7: ...abnormal operations Various alloy layers may be formed during transit of LPG gas in tanks depending on mixture compositions That causes a change in heating power of mixture assigned to the device and...

Page 8: ...er and by using elbows as low as possible At least 1 bar pressurized grid input water should be supplied to ensure adequate domestic hot water Hydrophore should be used if required Figure 10 Flue peri...

Page 9: ...plications Each 45 elbow usage requires to decrease maximum 50 cm from horizontal vertical distance 60 100 Conventional 90 Elbow 153 11 660 600009 It can be used in horizontal and or vertical flue app...

Page 10: ...elbow contacting with the restrictive set Place the External Wall Plate into the flue terminal as seen in Figure 11 12 for grouping the flue output terminal After placing the flue output terminal thr...

Page 11: ...rd Flue Set Elbow 90 b Flue Extension Pipe c Additional 90 Elbow d Standard Flue Set Pipe Figure 16 II Two 90 elbow sample flue installations d a b c a b c d 4 m Figure 15 I Single 90 bended sample fl...

Page 12: ...Hermetic Flue Type fire resistant insulation material is placed between the wall and exhaust gas relief pipe Materials used for manufacturing the combi are resistant against glycol and propylene based...

Page 13: ...sockets and extension cables are not allowed to use 2 2 17 Optional Controls Room Thermostat External Weather Temperature Sensor and Others Room thermostat Outside Temperature Sensor etc control devi...

Page 14: ...of the radiator Combi safety valve relief should be connected to a discharge cone Otherwise safety valve shall be activated and manufacturer shall not be responsible due to water discharge around the...

Page 15: ...s valve radiator and tap water valves If you will shut off the combi for a short period perform below written operations Do not close combi electrical fuse gas valve radiator and tap water valves Leav...

Page 16: ...screens consist of navy blue colored backlight LCD screen 2 buttons Radiator 3 and Hot Tap Water 4 and 2 pcs RESET 2 and MODE 1 pushbuttons RESET It is used for re starting the combi and eliminating t...

Page 17: ...en light turns off At that position you can adjust the temperature between 35 80 C with the Radiator CH temperature adjustment button 3 Temperature value increases when button is rotated clockwise or...

Page 18: ...if the pressure is lower than this value 18 Failure indicator The temperature value displayed on the combi screen has a 3 C tolerance depending on environmental conditions not arising from the combi...

Page 19: ...installation Hold the MODE button for switching on the combi when letter is available on the screen A cycle starts on the screen Release the button when cycle is completed In some cases combi initiall...

Page 20: ...er is seen as the screen screen light turns off your combi is now at STANDBY position Figure 31 Thermostat position Figure 32 Outside weather temperature sensor Figure 33 Outside temperature sensor op...

Page 21: ...zed Service according to your request Air Discharge Function Activating the menu for LAWA PRIWA and ENERWA models Air discharge function can be activated by pressing the RESET button more than 5 secon...

Page 22: ...ermittent contacts or open contacts on harness carefully 3 Check Domestic heating water temperature sensor ressistance 4 Check cabeling and connectors between NTC and board 5 Reset Restart boiler E 13...

Page 23: ...vice at first E 42 Buttons anomaly Boiler does not work E42 error code flashing on the screen Wrong parameters settled on TsP menu 1 Call For service E 43 Opentherm communication error Boiler does not...

Page 24: ...st perform Au To calibration E 78 Max regulation current value reached Boiler does not work E78 error code flashing on the screen Gas inlet pressure Aging or rust on the electrode Recirculation on flu...

Page 25: ...Au To calibration E 88 Fault of electronic gas valve managing circuit Boiler does not work E88 error code flashing on the screen Cabeling disconnections Gas valve failiure 1 Call for authorised servi...

Page 26: ...ration Temporary wind precence 1 If there is strong wind ie wind storm wait until the wind storm stop then keep using the boiler as it is 36 or 48 hours boiler try to remove half power mode by it self...

Page 27: ...ailures occurring due to transportation unloading loading storing external physical Crushing scratches fractures and chemical factors following delivery of the product 6 Damages and failures arising f...

Page 28: ...10 7 28 10 32 5 12 8 Max Domestic Hot Water flow rate t 30 C min 10 5 10 9 10 7 10 9 13 9 13 3 13 9 14 2 Maximum Minimum water pressure bar 10 0 3 10 0 3 10 0 3 10 0 3 Temperature adjustment range oC...

Page 29: ...2ELL I 2H I3P NUMBER OF CHOOSED CONNECTING CONDITIONS Used gas G20 G20 G25 G25 G20 G25 G20 G31 Countries of destination AT BG CH CZ DK EE ES FI GB GR IE IT LT LV NO PT RO SE SI SK DE LU PL RO BE FR NL...

Page 30: ...30 warmhaus com...

Page 31: ...been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold subject...

Page 32: ...CONVENTIONAL COMBI BOILERS INSTALLATION USER MANUAL LAWA LAWA PLUS Instruction booklet code of Lawa LawaPlus 150 11 606 000004 Revision Date 09 2020...

Reviews: