background image

22

warmhaus.com

Failure 

Code

Description of the Error

Malfunction

Probable Cause

Solution(s)

E 06

No ignition

Boiler does not work, E06 
error code flashing on the 
screen

> Gas supply failure

1-) RESET boiler at first check if problem removed 
2-) Check other gas devices if they are working
3-) Check main gas suppy valve is open or not
4-) Check boiler gas suppy valve bellow the boiler  is open or not 
5-) RESET boiler at first check if problem removed 
6-) Call for authorised service at first

E 07

Safety thermostat inter-
vention 

Boiler does not work, E07 
error code flashing on the 
screen

> Water pressure in the boiler 
not enough
> High Water pressure  
in the boiler higher  
than > 2,8 bar
> Domestic heating water 
temperature sensor faulty
> Central heating FLOW 
temperature sensor faulty
> Gas supply failure

1-) RESET boiler at first check if problem removed
2-) Check boiler central heating valves are open if they are closed open 
of all 
3-) Check all radiator valves are open if they are closed open of all 
minimum 3 meters of radiator must be open
4-) RESET boiler and check if problem removed
5-) Call for authorised service at first

E 08

Flame circuit failure

False flame signal from com-
bustion or electrode

> Water blokage on syphon
> Electronic board

1-) Call for authorised service at first

E 09

No water circulation in the 
system

Boiler does not work, E09 
error code flashing on the 
screen

> Lack of water on the system
> Pump blockage
> Pump failiure
> Pump harness
> Installation blockage

1-) RESET boiler at first check if problem removed
2-) Check boiler central heating valves are open if they are closed open 
of all 
3-) Check all radiator valves are open if they are closed open of all 
minimum 3 meters of radiator must be open
4-) RESET boiler and check if problem removed
5-) Call for authorised service at first

E 10

Central heating temperature 
RETURN sensor faulty

Boiler does not work, E10 
error code flashing on the 
screen

> Central heating  
RETURN temperature sensor 
faulty

1-) Call for authorised service at first

E 11

Gas valve modulator discon-
nected

Boiler does not work, E11 
error code flashing on the 
screen 

> Gas valve harness

1-) Call for authorised service at first
2-) Check gas valve cabeling between board and gas valve

E 12

DHW temperature Probe, in 
storage tank mode, fault

Boiler does not work, E12 
error code flashing on the 
screen

> Domestic heating water 
temperature sensor in stor-
age tank faulty

1-) Call for authorised service at first
2-) Check intermittent contacts or open contacts on harness carefully
3-) Check Domestic heating water temperature sensor ressistance 
4-) Check cabeling and connectors between NTC and board
5-) Reset & Restart boiler

E 13

Exhaust temperature probe 
over-temperature alarm

Boiler does not work, E13 
error code flashing on the 
screen

> Over temperature flue gas 
outlet value > 105 C°

1-) Call for authorised service at first

E 14

Exhaust ( FLUE ) temperature 
probe fault

Boiler does not work, E14 
error code flashing on the 
screen

> Central heating FLUE tem-
perature sensor faulty

1-) Reset & Restart boiler 
2-) Call for authorised service at first

E 15

Fan failure (feedback/supply) Boiler does not work, E15 

error code flashing on the 
screen

> Fan harness

1-) Call for authorised service at first
2-) Check intermittent contacts or open contacts on harness carefully 
on fan main supply, if main supply not connected then fan will not 
operate and boiler will not ignite
3-) Check intermittent contacts or open contacts on harness carefully 
on fan PWM connection, if PWM connection not connected then fan 
will work at %100 capacity
4-) Reset & Restart boiler

E 16

Central heating temperature 
RETURN sensor faulty

Boiler does not work, E10 
error code flashing on the 
screen

> Central heating RETURN 
temperature sensor faulty

1-) Call for authorised service at first
2-) Check intermittent contacts or open contacts on harness carefully
3-) Check RETURN Central heating temperature sensor ressistance 
according to page 93 at section 4.28 if its out of tolerance replace NTC
4-) Check cabeling and connectors between RETURN NTC and board
5-) Reset & Restart boiler

E 17

Temperature difference 
between FLOW and LIMIT 
NTC (Double Heating Probe)  
faulty

FLOW and LIMIT sensor             
( DOUBLE NTC)  malfunction

>  FLOW  and  LIMIT  Sensor               
( double NTC ) faulty

1-) Reset & Restart boiler 
2-) Call for authorised service at first

E 19

Water flow selection with wa-
ter flow meter input reading

Lack of domestic heating 
water on request

Wrong parameters settled on 
TsP menu

1-) Call for authorised service at first
2-) Only authorised service must adjust TsP Parameter P01=0 with 
defalut value

E 20

CH Overtemperature, Tem-
perature Central Heating > 
TSP 81 value °C

Boiler does not work, E81 
error code flashing on the 
screen

> Lack of water on the system
> Pump blockage
> Pump failiure
> Pump harness
> Installation blockage

1-) RESET boiler at first check if problem removed
2-) Check boiler central heating valves are open if they are closed open 
of all 
3-) Check all radiator valves are open if they are closed open of all 
minimum 3 meters of radiator must be open
4-) RESET boiler and check if problem removed
5-) Call for authorised service at first

Summary of Contents for LAWA 18

Page 1: ...CONVENTIONAL COMBI BOILERS INSTALLATION USER MANUAL LAWA LAWA PLUS...

Page 2: ...Lawa LawaPlus Enerwa E24 EnerwaPLUSE24...

Page 3: ...2 2 16 Installation at Partially Protected Exteriors 12 2 2 17 Electrical Connections 12 2 2 18 Optional Controls Room Thermostat External Weather Temperature Sensor and Others 13 2 3 HYDRAULIC INSTA...

Page 4: ...under any circumstances during installation use or maintenance operations and device warranty shall also be void Only the authorized Warmhaus Service is authorized to make the electrical connection o...

Page 5: ...r matches Close valves of devices operating with natural gas and your gas meter Immediately evacuate the place with gas odour Natural Gas Emergency Line from your neighbour or another suitable place D...

Page 6: ...lace Wall installation for the combi boiler should be well secured The hanger plate given as standard with the combi should be installed according to the technique to a full or semi full brick wall ac...

Page 7: ...abnormal operations Various alloy layers may be formed during transit of LPG gas in tanks depending on mixture compositions That causes a change in heating power of mixture assigned to the device and...

Page 8: ...er and by using elbows as low as possible At least 1 bar pressurized grid input water should be supplied to ensure adequate domestic hot water Hydrophore should be used if required Figure 10 Flue peri...

Page 9: ...plications Each 45 elbow usage requires to decrease maximum 50 cm from horizontal vertical distance 60 100 Conventional 90 Elbow 153 11 660 600009 It can be used in horizontal and or vertical flue app...

Page 10: ...elbow contacting with the restrictive set Place the External Wall Plate into the flue terminal as seen in Figure 11 12 for grouping the flue output terminal After placing the flue output terminal thr...

Page 11: ...rd Flue Set Elbow 90 b Flue Extension Pipe c Additional 90 Elbow d Standard Flue Set Pipe Figure 16 II Two 90 elbow sample flue installations d a b c a b c d 4 m Figure 15 I Single 90 bended sample fl...

Page 12: ...Hermetic Flue Type fire resistant insulation material is placed between the wall and exhaust gas relief pipe Materials used for manufacturing the combi are resistant against glycol and propylene based...

Page 13: ...sockets and extension cables are not allowed to use 2 2 17 Optional Controls Room Thermostat External Weather Temperature Sensor and Others Room thermostat Outside Temperature Sensor etc control devi...

Page 14: ...of the radiator Combi safety valve relief should be connected to a discharge cone Otherwise safety valve shall be activated and manufacturer shall not be responsible due to water discharge around the...

Page 15: ...s valve radiator and tap water valves If you will shut off the combi for a short period perform below written operations Do not close combi electrical fuse gas valve radiator and tap water valves Leav...

Page 16: ...screens consist of navy blue colored backlight LCD screen 2 buttons Radiator 3 and Hot Tap Water 4 and 2 pcs RESET 2 and MODE 1 pushbuttons RESET It is used for re starting the combi and eliminating t...

Page 17: ...en light turns off At that position you can adjust the temperature between 35 80 C with the Radiator CH temperature adjustment button 3 Temperature value increases when button is rotated clockwise or...

Page 18: ...if the pressure is lower than this value 18 Failure indicator The temperature value displayed on the combi screen has a 3 C tolerance depending on environmental conditions not arising from the combi...

Page 19: ...installation Hold the MODE button for switching on the combi when letter is available on the screen A cycle starts on the screen Release the button when cycle is completed In some cases combi initiall...

Page 20: ...er is seen as the screen screen light turns off your combi is now at STANDBY position Figure 31 Thermostat position Figure 32 Outside weather temperature sensor Figure 33 Outside temperature sensor op...

Page 21: ...zed Service according to your request Air Discharge Function Activating the menu for LAWA PRIWA and ENERWA models Air discharge function can be activated by pressing the RESET button more than 5 secon...

Page 22: ...ermittent contacts or open contacts on harness carefully 3 Check Domestic heating water temperature sensor ressistance 4 Check cabeling and connectors between NTC and board 5 Reset Restart boiler E 13...

Page 23: ...vice at first E 42 Buttons anomaly Boiler does not work E42 error code flashing on the screen Wrong parameters settled on TsP menu 1 Call For service E 43 Opentherm communication error Boiler does not...

Page 24: ...st perform Au To calibration E 78 Max regulation current value reached Boiler does not work E78 error code flashing on the screen Gas inlet pressure Aging or rust on the electrode Recirculation on flu...

Page 25: ...Au To calibration E 88 Fault of electronic gas valve managing circuit Boiler does not work E88 error code flashing on the screen Cabeling disconnections Gas valve failiure 1 Call for authorised servi...

Page 26: ...ration Temporary wind precence 1 If there is strong wind ie wind storm wait until the wind storm stop then keep using the boiler as it is 36 or 48 hours boiler try to remove half power mode by it self...

Page 27: ...ailures occurring due to transportation unloading loading storing external physical Crushing scratches fractures and chemical factors following delivery of the product 6 Damages and failures arising f...

Page 28: ...10 7 28 10 32 5 12 8 Max Domestic Hot Water flow rate t 30 C min 10 5 10 9 10 7 10 9 13 9 13 3 13 9 14 2 Maximum Minimum water pressure bar 10 0 3 10 0 3 10 0 3 10 0 3 Temperature adjustment range oC...

Page 29: ...2ELL I 2H I3P NUMBER OF CHOOSED CONNECTING CONDITIONS Used gas G20 G20 G25 G25 G20 G25 G20 G31 Countries of destination AT BG CH CZ DK EE ES FI GB GR IE IT LT LV NO PT RO SE SI SK DE LU PL RO BE FR NL...

Page 30: ...30 warmhaus com...

Page 31: ...been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold subject...

Page 32: ...CONVENTIONAL COMBI BOILERS INSTALLATION USER MANUAL LAWA LAWA PLUS Instruction booklet code of Lawa LawaPlus 150 11 606 000004 Revision Date 09 2020...

Reviews: