33
warmhaus.com
Transparent Parameters Menu (TSP)
Designation :
All Warmhaus Wallhung Boilers
Object
Type-model(s)
Burner Control Transparent Parameter List
Parameter no.
Parameter
Value Field
MINERWA 25
Default
P32
Maximum power fan speed ( P32 x 25 + 2000 rpm )
P33 - 255
184 = NG
174 = LPG
P33
Minimum power fan speed ( P33 x 25 rpm )
30 - 60
34 = NG
34 = LPG
P34
Pump PWM Max speed
30-100
100
P35
Pump PWM Min speed
30-P34
55
P36
F49 Offset
0 - 100
50
P37
Configuration Aux probe
3 - 3
3
3 = Return temperature NTC
P38
Antifreezing activation temperature ( C° )
0 - (+10 C° )
5
P39
CH post circulation time ( value 1 = 10 seconds )
0 - 99 sec x 10
18
P40
Delay in the activation of CH ignition after DHW request ( value 1 = 10 seconds, if Preheat adjusted time =
value / 2
0 - 60 sec x 10
12
P41
Sanitary modulation with Fluxmeter
0 – 1
1
0 = Disconnected
1 = Connected
P42
DHW Preheat function configuration ( Please check P18 first )
0 – 1
0
0 = Pre heat OFF / PrE - OFF
1 = Pre heat ON / PrE - On
P43
Delay of DHW activation with solar config. ( value 1 = 1 second )
0 - 30 sec
0
P44
Pressure switch selection
0 – 2
1
0 = Water pressure switch
1 = Water pressure sensor - Alarm Level > 2,8 Bars
2 = Water pressure sensor - Alarm Level > 3,8 Bars
P45
Antilegionella function (storage tank only)
54 / 55 - 80
54
54 = Disabled
P46
Modulating pump speed selection (optional)
0 – 1
1
0 = No modulation
1 = Automatic modulation in range of %66 - %100
P47
Delta temperature CH flow and return for pump modulation
10 – 40
20
P48
Pump configuration
0 – 1
0
0 = Intermittent
1 = Continuous
P49
OEM Menu Enabled ( P49 = 49 enable read/write of following parameters)
0 – 99
0