WARNING: Minimum requirement: Incorporate 1 vent on at least two opposing sides (2 vents total) at a minimum size of 18 sq. inches each (Example:
3”x 6” or larger). Installation of the vents in the mid to lower area of the enclosure is recommended. Ventilation allows for heat and/or residual fuel to
escape. Failure to properly vent enclosure may result in the fire pit overheating or explosion. Overheating could lead to heat damage to internal compo-
nents. Some enclosures may require more ventilation based on material, size, and extended use. The vent may serve as a drain as well when installed at
bottom sidewall to prevent water build up. Always consult with local municipality regarding any local code requirements.
WARNING: Ready-to-Finish Kits come with Fire Pit Vent Kit (FPVK). Vents do not come pre-installed on Ready-to-Finish Kit as placement and installation
depends on veneer. Vents to be installed by contractor on site.
60K – 120K BTU System with 1/2" Flex Line (FLKV12)
Original Series: CFB60, CFB84, CFB120 | Linear Series: CFBL90, CFBL110 | H-Style Series: CFBH120
Any custom burners between 60K - 120K
FOR PUSH BUTTON IGNITION INSTRUCTIONS: Follow Match Lit System installation instructions. When finished, turn
to page 26 for Push Button Ignition installation instructions.
•
Select key valve location on your fire pit.
•
Plumb your existing gas supply into one side of your key valve.
•
Position your preferred support materials for the burner & plate inside of your fire pit (i.e., cinder blocks, elbow
brackets, etc.)
•
Warming Trends recommends a 4” clearance from the finished top of your fire pit (capstones) to your plate.
•
For Match Lit burners, Warming Trends
TM
recommends a minimum 6” clearance below plate for
additional connections.
•
For Electronic Ignition burners, Warming Trends
TM
recommends a minimum of 16" - 20" clearance below plate
for additional connections.
•
Use thread sealant that is resistant to all gases on all fittings except flared fitting to flex line connections.
•
Be sure to tighten every joint securely. Use thread sealant where required.
•
Perform leak tests on all fittings before turning on ignition.
B
R
A
S
S
B
U
R
N
E
R
S
60K – 120K BTU System with FLKV12
4” Key
12” Key
Key Valve
Pressure
Face Plate
Flex Line
STEP 1:
Locate FLKV12
Parts include 1/2” flex line, key valve and keys (4 and 12 inch.)