13
121K - 249K BTU Systems with
3/4" Flex Line (FLKV34) or
3/4" Flex Line + FIT180 (FLKV34FIT180)
Original Series: CFB180 | Linear Series: CFBL130, CFBL150, CFBL190, CFBL210 | H-Style Series: CFBH160, CFBH200,
CFBH240 Any custom burners between 121K - 249K
FOR PUSH BUTTON IGNITION INSTRUCTIONS: Follow Match Lit System installation instructions. When finished, turn
to page 26 for Push Button Ignition installation instructions.
STEP 3
STEP 3:
Connect your FIT180 fitting to
the inside threads of one of the 3/4” flared
fittings removed in Step 3.
Apply thread sealant here
1/2" x 2" Nipple (FIT180)
3/4" Flare Fitting
Use inside threads
of flared fitting
STEP 2:
Remove 3/4” flared fittings from
each end of 3/4” flex line.
Flex Line
3/4" Flare Fitting
121K - 249K BTU Systems with FLKV34 and FLKV34FIT180
STEP 1 - FIT180
FIT180: 1/2" x 2" Nipple
4” Key
12” Key
Key Valve
Pressure
Face Plate
Flex Line
STEP 1:
Locate FLKV34
Parts include 3/4” flex line, key valve and keys (4 and 12 inch)
and FIT180.
WARNING: Minimum requirement: Incorporate 1 vent on at least two opposing sides (2 vents total) at a minimum size of 18 sq. inches each (Example:
3”x 6” or larger). Installation of the vents in the mid to lower area of the enclosure is recommended. Ventilation allows for heat and/or residual fuel to
escape. Failure to properly vent enclosure may result in the fire pit overheating or explosion. Overheating could lead to heat damage to internal compo-
nents. Some enclosures may require more ventilation based on material, size, and extended use. The vent may serve as a drain as well when installed at
bottom sidewall to prevent water build up. Always consult with local municipality regarding any local code requirements.
WARNING: Ready-to-Finish Kits come with Fire Pit Vent Kit (FPVK). Vents do not come pre-installed on Ready-to-Finish Kit as placement and installation
depends on veneer. Vents to be installed by contractor on site.