background image

14 June 2016 

Due to continued product improvement, Warmington Ind LTD reserves the right to change product specifications without prior notification. 

All Dimension are in mm 

10 

PROCEDURE FOR THE TEST AND COMISSIONING OF YOUR DECORATIVE FIRE.

 

 

Ensure Gas Supply and the Power Supply (caution 240V) to the Unit. 

 

Refer to Data Plate  on this Specification for settings. The Data Plate is attached to the under carriage of 
the Burner. 

 

 

Remove Front Grate ensure the CAT5 cable to the Control Receiver is still connected. 

 

 

Loosen the Jet Test point and attach manometer (Digital is preferred). The Test Point is on the Right 
Hand Side of the Gas Burner, as Shown Below. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Light Appliance, adjust to High Flame setting and check pressure, adjust to Low Flame and check pres-
sure. 

 

 
NOTE: If setting the Pressure is required it is to be carried out by a Certified Gas Fitter.

 

 

 

If adjustments are necessary, remove the cap. The Pressure Adjustment Screw and Nut are on the Front 
Side of the Gas Control Valve (shown in Diagram 

in this specification) and are 

Factory 

set. 

 
 
  

High Pressure Setting

: Set the modulator to Maximum Condition. Screw in 

Nut A 

to Increase the Outlet Pres-

sure then screw Nut A out to Decrease the Pressure to the desired settings. Use 10mm spanner. 
 
 

Low Pressure Setting: 

Turn Off the Power to the Modulator and keep Nut A stationary. Use a screwdriver to 

screw in 

Screw B 

to Increase the Pressure and Screw it Out to Decrease the Pressure. Carefully replace the 

Modulator Plastic Cap. 
 
 

WARNING: 

To ensure the Correct Operation of the Modulator it is necessary that the Plastic Cap is returned to 

its original location. 
 

Gas Test Nipple 
for SG/EG Fires 

Summary of Contents for SG 1100

Page 1: ...ion The Warmington unit is to be installed by a certified Warmington installer or an approved NZHHA installation technician See www homeheat co nz members for a certified NZHHA SFAIT Installer in your...

Page 2: ...on the pressure difference from inside the building to the outside A lower pressure in the building may induce a draft down the flue system and back into the building causing the fire to smoke or spil...

Page 3: ...rner Width A 674 754 874 1074 Burner Height B 205 205 205 205 Burner Depth C 272 272 272 272 Flue Diameter Min J 200 200 250 250 Flue CSA mm K 31 416 31 416 49 087 49 087 WARMINGTON BURNERS NOTE IMPOR...

Page 4: ...ctor Size mm 2 X 1 1mm 2 X 1 2mm 2 X 1 3mm 2 X 1 4mm Burner Pressure High kPa 2 5 2 5 2 5 2 5 Burner Pressure Low kPa 0 75 0 75 0 75 0 75 MJ h 29 38 42 50 Flame Effect Output Only Effect Effect Effect...

Page 5: ...hat the Gas Type Specified on the Data Plate is correct for the available supply LPG or NG A Copper Gas supply capable of supplying the correct MJ h should be brought into the rear of the Installation...

Page 6: ...roughest Face Outward Ensure Coal positioning does not directly block the 3 Flame Pilot The placement of the Coals Logs may vary to make an even Flame Pattern Logs and Twigs may be scattered to achie...

Page 7: ...ng the Switch in a Depressed State repeat steps 2 3 if necessary Once the Pilot Flame is lit hold this position for 3 5 seconds release from the Depressed State before setting the Flame Control to Ful...

Page 8: ...rol Valves are Factory Set but may require adjustment onsite Turn Appliance Off Remove Front Plastic Cover on Igniter Pull Cover to Slide off Unscrew Test Nipple on the Burner Manifold fit the Test Ga...

Page 9: ...es on the principle of dual radiant and convected heat Therefore it is important to observe the following precautions associated with any heating appliance or open fire Do not cover or restrict the fi...

Page 10: ...adjust to Low Flame and check pres sure NOTE If setting the Pressure is required it is to be carried out by a Certified Gas Fitter If adjustments are necessary remove the cap The Pressure Adjustment S...

Page 11: ...serviced annually and any service operation must be carried out by a qualified service person WARNINGS WARNING ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRITING BY THE TESTING AU...

Reviews: