7 October 2021

 

Due to continued product improvement, Warmington Ind LTD reserves the right to change product specifications without prior notification.

 

All Dimension are in mm

………….

Copyright © 

 

1

 

GAS OPEN FIRES 

Installation Instructions into Wood or Block Alcoves

 

SG & EG 600

-

700

-

780

-

900

-

1100

 

The fireplace is constructed and tested to comply with NZS 4558(int):2013 

Decorative gas log and other fuel effect appliances

”.

 

 

Keep these instructions for further reference. Ensure that you have the correct and current installation details for the Warmington fireplace.

 

 

Installation

 

The Warmington unit is to be installed by a certified Warmington installer or an approved NZHHA installation technician.

 

See www.homeheat.co.nz/members for a certified NZHHA SFAIT Installer in your area.

 

A licenced certified gas fitter and licenced electrician are required to run power and gas supplies as required to the unit and any commissioning as part of the 

installation process.The heater must be installed according to these instructions and in compliance with all relevant building, gas fitting, electrical and other 

statutory regulations.

 

 

IMPORTANT 

Read all the instructions carefully before commencing the Installation. Failure to follow these instructions may result in a fire hazard and void the warranty 

Related documents 

Fire and flue system installation, and instructions to comply with NZS 5601.1:2013, 

3645.1(Int):2010, 3645.2(Int):2010, 5266:2014, 2918:2001. 

Warmington Flue System

 

Timber Framing

 

Hearth

 

Warm Air Outlet

 

Vent

 

Cool Air 

Caitec 

Vents

” 

Inlet Vent

 

Warmington Gas Firebox

 

Warmington Gas Cowl 

 

                           S/S Flashing

 

 

(Top venting can also be 

through S/S flashing.

 

See flashing detail in spec)

 

Summary of Contents for SG 600

Page 1: ...NZHHA SFAIT Installer in your area A licenced certified gas fitter and licenced electrician are required to run power and gas supplies as required to the unit and any commissioning as part of the ins...

Page 2: ...ical system to ensure that there is always a neutral or positive pressure at the fireplace and a negative pressure at the flue outlet This will ensure that the draft in the flue system is always to th...

Page 3: ...95 675 Insulation Kit Height G 620 620 620 620 620 Insulation Kit Depth H 485 485 485 485 485 Centre of Flue I 315 315 285 285 321 Flue J 200 200 250 250 150 Flue Liner K 250 250 300 300 200 Fascia Wi...

Page 4: ...rner Pressure Low kPa 0 75 0 75 0 75 0 75 0 75 MJ h 29 38 42 50 26 Flame Effect Output Only Effect Effect Effect Effect Effect Supply Pipe Size dia min 3 8 3 8 1 2 1 2 3 8 Natural Gas Nominal Pressure...

Page 5: ...Cell Clearance Depth Q 535 535 535 535 535 Hearth Width R 1100 1180 1300 1500 1000 Hearth Projection S 300 300 300 300 300 Chimney Chase Clearance T 350 350 400 400 300 Window Height V 660 660 660 66...

Page 6: ...G EG 1100 SG EG 600 Hearth Width R 1100 1180 1300 1500 1000 Hearth Projection S 300 300 300 300 300 Alcove Width O 810 895 1010 1210 690 Alcove Depth Q 535 535 535 535 535 Centre of Flue I 315 315 285...

Page 7: ...G 1100 SG EG 600 Heat cell Clearance Width OO 810 1210 1210 1210 690 Alcove Clearance Height PP 2400 2400 2400 2400 2400 Alcove Clearance Depth QQ 600 600 600 600 600 Window Height VV 630 630 630 630...

Page 8: ...to comply with the current standards IF FLASHING CONE NEEDED 1 NOTE The last length of flue pipe needs to extend past the liner so that when the top spider and the Flashing cone are fitted that the f...

Page 9: ...1041 20th July 2004 FLUE PENETRATION vented through alcove double lined flue system FLUE PENETRATION Vented through Top Flashing Note External requirements Refer to relevant standards Install flue sys...

Page 10: ...Y CHASE FLASHING AND AIR VENTILATION OPTIONS VENTING THROUGH CHIMNEY CHASE No Insulation under flashing VENTING THROUGH FLASHING Insulation under flashing Note Flashing spigot height is determined by...

Page 11: ...ange product specifications without prior notification All Dimension are in mm Copyright 11 FLUE HEIGHT MINIMUM DETAILS FRAME OUT AND TRIM OUT DETAILS FOR CHIMNEY CHASE The flue exit is to comply to r...

Page 12: ...LTD reserves the right to change product specifications without prior notification All Dimension are in mm Copyright 12 COMBUSTIBLE MANTLE CLEARANCES RAISED HEARTH CLEARANCES Note For Combustible Floo...

Page 13: ...GAS SUPPLY ELECTRONICS LOCATION Firebox SG EG 700 SG EG 780 SG EG 900 SG EG 1100 SG EG 600 From Base Of Firebox AA 86 86 86 86 86 From Centre Of Firebox BB 275 315 375 475 215 Plinth CONCEPT THROUGH...

Page 14: ...fied on the Data Plate is correct for the available supply LPG or NG A Copper Gas supply capable of supplying the correct MJ h should be brought into the rear of the Installation Cavity through the ho...

Page 15: ...coals onto the Vermiculite Base 2 Top Row Assemble 2 top rows of coals onto the bottom row Each coal randomly posi tioned with the torn roughest facing outward Ensure coal positioning does not directl...

Page 16: ...to light all the way across Once the flame is established adjust to the desired setting and close the cover To shut down Open the cover by pulling it outwards Turn the control ignition switch to PILOT...

Page 17: ...pressure see spec s Extinguish Appliance remove test equipment and secure test nipple Check valve burner for correct operation check fire for gas leaks Note When the base screw is removed gas will le...

Page 18: ...to observe the following precautions associated with any heating appliance or open fire Do not cover or restrict the fireplace upper or lower vents in any way as this may result in a build up of hazar...

Page 19: ...Copyright 19 Option 2 Three speed fan as additional option on SG units or EG units without remote controlled electronics eg units with on off hi low switches on the wall Option 1 Single speed fan as...

Page 20: ...urner will operate any pressure between the hi and the low pressures DIAGRAM B SHOWING CONTROL VALVE WITH TEST POINTS AND ADJUSTING SCREW After checking the pressure turn the unit off remove manometer...

Page 21: ...Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification All Dimension are in mm Copyright 21 EG ON OFF ONLY SIT840 valve...

Page 22: ...r river rocks to achieve their full flame pattern and glow During the initial burn period some smoke and smell may be experienced Because of this run the appliance on the high po sition in a well vent...

Page 23: ...Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification All Dimension are in mm Copyright 23 GAS STARTER SCHEMATIC DIAGRA...

Page 24: ...y Press and hold the or button for 2 seconds or longer to in crease or decrease the day of the week by 1 day every 0 5 seconds Press OK to complete setting The time and day of the week is now set SETT...

Page 25: ...WE TH FR MO TU WE TH FR SA SU SU SA MO TU WE TH FR SA SU To accept the selected day s of the week press OK First period s start time The display will indicate P1 on the top The Hour and AM PM setting...

Page 26: ...le com store apps details id com millec intelligythermostatmkii Or search for Intelligy Thermostat MKII in your smart phone app store For instructions on how to push the appliance to your Wi Fi please...

Page 27: ...first and once this is on it will ignite the main burner Pressing and releasing the power button again will switch off the appliance When the appliance is turned on the gas fire will be set to medium...

Page 28: ...s to pressure is to be carried out by a Certified Gasfitter If adjustments are necessary remove the cap The Pressure Adjustment screw and nut are on the front side of the Gas Control Valve shown in di...

Page 29: ...atisfied that the appliance is working correctly fit the front panel assembly back to the gas burner NOTE Ensure you peel the Protective Plastic Coating from any stainless steel components if fitted A...

Page 30: ...1 Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification All Dimension are in mm Copyright 30 FULLY MODULATING SIT 845 W...

Page 31: ...ate building codes This appliance must be serviced annually and any service operation must be carried out by a qualified service person WARNINGS WARNING ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT...