PELLET STOVES 9 PS45 CLASSIC 151211-24
45
90
Vent Termination Requirement
1. Do not terminate the vent in any enclosed or semi-enclosed
areas such as a carport, garage, attic, crawlspace, narrow
walkway, closely fenced area, under an enclosed sundeck or
porch, or any location that can build up a concentration of fumes
such as stairwells, covered breezeway, etc.
2. Termination must exhaust above the inlet elevation. It is
recommended that at least fi ve feet of vertical pipe be installed
in the vent system. This will create a natural draft to prevent
the possibility of smoke or odor during appliance shut down or
power failure and avoid exposing people or landscaping shrubs
to high temperatures.
Hooded vent
Using existing
wood vent
Thru -roof
Recommended
Recommended
Recommended
Fig #5
Storm collar
Roof fl ashing
Rain Cap
5ft
(150cm)
rise
CAUTION
This Installation may
cause problems during
adverse weather or power
failure.
3 .Vent surfaces can become hot enough to cause burns
if touched. Non-combustible shielding or guards may be
required.
4. The Vent must terminate a minimum of 12 inches (30 cm)
from the wall. Vertical termination must protrude a minimum of
24" (60 cm) from the roof surface.
5. Locate the vent termination at least two feet away from
combustible materials such as shrubs, plants, grass, fences,
roof overhangs and adjacent buildings.
Summary of Contents for PS45 Classic Series A
Page 19: ...PELLET STOVES 19 PS45 CLASSIC 151211 24 Wiring Diagram 5050 838 A 010210 PS 45 WIRING...
Page 21: ...PELLET STOVES 21 PS45 CLASSIC 151211 24 a a b b Components List A B...
Page 22: ...PELLET STOVES 22 PS45 CLASSIC 151211 24...
Page 23: ...PELLET STOVES 23 PS45 CLASSIC 151211 24 Rating Label...