DO NOT
cut or shorten the Wall Heating panel at any time.
DO NOT
allow the heating panel to cross expansion joints of the building or
structure.
DO NOT
alter the spacing of the mat at anytime.
DO NOT
allow the wall heating panels to exceed a maximum of 40°C. This is
achieved by installing a Warmup Thermostats with temperature sensor.
DO NOT
connect the heaters in series, the heating panels must be connected in
parallel.
DO NOT
allow the heating element wire to touch or cross at any point.
DO NOT
install this product behind any other material other than ceramic or
natural stone tiles.
DO NOT
extend heating panels beyond one wall surface, always use separate
panels for each wall.
DO NOT
leave any of the wire exposed. The heating panel must be completely
embedded in flexible tile adhesive, including the cold lead and end termination
joints. Failure to follow this instruction can cause the heating element to overheat.
DO NOT
cover the heating panel manufactured joints with tape, you may if
necessary tab tape the joint to hold it in place before embedding in flexible tile
adhesive.
DO NOT
cover the wall heating panel until it has been inspected ,and thoughly
tested by a certified electrician. All measurements and results
must
be logged on
the control card found at the end of this instruction manual.
DO NOT
switch on the heating panel until all adhesive and grouts have been
allowed to dry as per the manufactures instructions.
DO NOT
attempt to carry out any DIY repairs on this product, if you damage the
heater during installation contact Warmup Technical Support on 0845 345 2288.