background image

5

CONTROLLING YOUR ROOF & GUTTER CABLE INSTALLATION

The Warmup Roof & Gutter De-Icing Cable works most effectively with an automatic thermostat and sensing 
device. The sensor monitors for moisture and temperature to maintain the required temperature. 
For outdoor mounted controls, use the DS-series of automatic controllers, the Commbox and the TRF-115.
For indoor-mounted devices, select the ETO2, USETOG module with USETOR roof sensor(s) and USETOK mounting 
tube for ground sensor USETOG.

When using the NAMSR-Kits from Warmup, no control device is necessary. Simply plug into an outdoor rated 
outlet supplied by a GFCI breaker of the appropriate voltage. 

ELECTRICAL PROVISIONS FOR THE SYSTEM 

The electrical connections to the De-Icing Cables shall be in accordance with the National Electrical Code (in the 
USA) or Canadian Electrical Code (in Canada).

INSTALLING YOUR ROOF & GUTTER HEATING CABLE

Choose a starting point

 - Select the starting point of your system by locating the desired placement of the 

outdoor electrical outlet or the junction box routing to the controller. Make sure to use caution and avoid high 
traffic areas, restrict general access to the cable and stay away from windows, doors and other obtrusions.

Plan the pattern on your roof

 - There are multiple methods for applying the cable to the roof and gutters 

as further described in this manual. We recommend you plan a written route for the cable to ensure the most 
efficient path and installation method for the heating cable.
 

Note that the heating cable is specifically intended for problem areas and does not need to be installed on all 

areas of the roof. In some instances, on high-pitched roofs (over 40 degree slope) and on roofs with minimal 

overhang, no cable on the actual roof line may be required. However, always ensure to create a path for the 

ice to melt from the roof to the ground, placing cable on the roof, in the gutters and in the downspouts as 

necessary. Extend the cable about 1’ out of the bottom of the downspout (surface) or about 1’ below the frost 

line. As a reference, the frost line in cold areas is typically 20” to 30” deep.

SERVICE

1. Prior to the winter season, make sure gutters and downspouts are free of leaves and other debris. 

2. Warmup recommends checking the insulation resistance of the heating cable sheath with a 2500 VDC 
meggar. This reading is taken at the power connection end of the cable between a buss wire and the grounding 
braid. The minimum acceptable reading is 20 megohms. The value should be recorded. 

3. The installation should be checked every Fall. The following checks should be done. 

A. Meggar test (see #2 above for procedure). 
B. Inspect heating cable and connections for signs of damage. 
C. If physical damage is found, replace the damaged sections. 

D. If the installation fails the meggar test and physical damage cannot be found, then the complete circuit 
should be removed and replaced with new roof and gutter heating cable. 

4. Prior to repairs performed on roof, heating cable must be removed to prevent damage to cable. Cable must 
not be exposed to chemical sealants that may be applied to roof surface and must be stored away from area 
while sealants cure. Upon replacement of cable, inspect for signs of physical damage to cable and connections. 
Replace any damaged sections and connections.

Summary of Contents for NAMSR-5W-120

Page 1: ...RTANT Read this manual before attempting to install your heating system Incorrect installation could damage the heating system and will invalidate your warranty Installation Manual Cable for Roof Gutter De icing The world s best selling electric floor heating brand ...

Page 2: ...3 After removing the cable from the carton or wrapping check the insulation resistance of the unit from buss wires to braid with a 2500VDC megger to assure the cables have not been damaged during shipping and handling ELECTRIC SHOCK HAZARD Verify insulation resistance is 20 megohms or greater before installing Contact Warmup if cable is less than 20 megohm SIZING GUIDE Service voltage 110 120V 220...

Page 3: ...ircuit conductor and the rating or setting of overcurrent devices shall not be less than 125 of the ampere load of the cable or units WARNING ELECTRIC SHOCK HAZARD Disconnect all power before installing or servicing heating cable and accessories A qualified person must perform installation and service of heating cable and accessories Heating cable must be effectively grounded in accordance with th...

Page 4: ...oped in the downspout if it is convenient to do so such as when a downspout is not at the end of a run Note Tee splices are not permitted and void agency approvals E Use a Warmup downspout hanger to protect the heating cable from damage caused by sharp gutter edges and to provide strain relief F Protect any heating cable which protrudes past the lower opening of the downspout 4 Installing the inst...

Page 5: ...r problem areas and does not need to be installed on all areas of the roof In some instances on high pitched roofs over 40 degree slope and on roofs with minimal overhang no cable on the actual roof line may be required However always ensure to create a path for the ice to melt from the roof to the ground placing cable on the roof in the gutters and in the downspouts as necessary Extend the cable ...

Page 6: ...rmup s 24 7 Toll Free Technical Number US 1 888 927 6333 CAN 1 888 592 7687 PLANNING YOUR LAYOUT Draw a plan showing the layout and location of the snow melting cables below and keep it for future reference ...

Page 7: ...e Figure 3 FIGURE 2 Triangle pattern along the roof line FIGURE 1 Typical pattern along roof line and in gutters downspouts Pattern for the roof line The cable laid along the roof line is arranged in a triangular pattern see Figure 2 The cable MUST extend above the overhang into the heated section of the roof To determine the height of the triangles measure the depth of the overhang The triangle h...

Page 8: ...could also use a tape to measure each section of the downspout To calculate the total cable needed add the measurements in each section and multiply by 2 Lastly if it is not possible to use either of these above methods you may use the cable itself to estimate the length of cable needed in the downspout However to avoid snagging or cutting the cable on sharp edges take care when pulling the cable ...

Page 9: ...M POWER KIT Power Connection Kit for Self Regulating Cable Includes 2 warning labels ROOF CLIP Roof Clips Sold 50 pkg NAM SPLICE KIT Splice Tee Kit for Self Regulating Cable NAM END KIT End Seal Kit for Self Regulating Cable ASE DS8 Automatic controller with built in moisture sensor and 30A relay TRF 115 007 Line Voltage Controller 120 227V NEMA 4x enclosure with remote temperature sensor CDP 2 In...

Page 10: ...r broken pipes in the event of equipment failure 10 Changes in the appearance of the product that does not affect its performance 11 The owner or his her designated representative attempts to repair the product without receiving prior authorization from Warmup Upon notification of a repair problem Warmup Inc will issue an Authorization to Proceed under the terms of this Warranty If Warmup is requi...

Page 11: ... Danbury CT 06810 Tel 1 888 927 6333 Fax 1 888 927 4721 E mail us warmup com Web www warmup com CANADA Warmup Inc 374 Wellington St W Toronto ON M5V 1E3 Tel 1 888 592 7687 Fax 905 366 7324 E mail ca warmup com Web www warmup ca International Flooring Center Inc 5047 W Jefferson Blvd Los Angeles CA 90016 Tel 323 731 8453 www FlooringSupplyShop com ...

Reviews: