background image

Step 5 - Install floor sensor

Place the floor sensor below the fibreglass mesh. The floor sensor must be installed 

centrally between the two runs of heating element and should extend a minimum 

of 150mm into the heated area. Secure the sensor to the floor using tape. 

NOTE: DO NOT TAPE OVER THE SENSOR TIP. 

It is best to avoid placing the floor sensor in areas of heat fluctuations e.g. 

near hot water pipes or radiators. It may be necessary to cut a channel in the 

floor to ensure that the floor sensor and power supply cable are kept at the 

same height as the heating element. 

When installing the floor sensor (located in the thermostat box) DO NOT 

cross over or under the heating element. 

At this stage the floor sensor must also be tested. Check the resistance of 

the floor sensor using your multi-meter (20K ohms). You should get a reading of 

approximately 9-23K ohms depending on the room temperature. 

If you do not get a reading your floor sensor may be damaged. If this is the case call 

the Warmup Technical Helpline to request a replacement. 

NOTE: The sensor may be extended up to 50m.

 

Step 6 - Fit Power Leads

Each mat is fitted with a single power lead for connecting the mat to the 

thermostat. To ensure the power lead remains at the same level as the 

heating element, you may need to cut or chisel a channel in the subfloor. 

When doing this take care not to damage the heating element. Secure the 

power lead in place using tape but do not tape over the manufactured joint 

where the power supply cable meets the heating element.

The power lead will go into the electrical trunking/conduit up to the 

thermostat. It is possible to extend the power lead using twin and earth 

cable.

Note: Instructions for fitting the Warmup® thermostat are included in the 

thermostat box. 

Step 7 - Tile & grout the floor 

Ensure you use tile adhesives and grouts suitable for use with underfloor 

heating systems (they must contain a flexible additive). It is important that 

each tile is solidly bedded in adhesive, with no air gaps or voids beneath. (2 

Part Flexible Adhesive). Do NOT dot and dab the tiles. 

Check with the manufacturers of the adhesive to ensure suitability.

Use a plastic notched trowel to move the adhesive along the element. Use a 

piece of cardboard on top of the exposed element to use as a crawl board. 

Ensure to test the resistance of the heating mat regularly during tiling to 

check the mat hasn’t been damaged during tiling.

If using flexible levelling compound before tiling make sure that the mat is 

completely flat, extra tape can be used to secure the edges of the fibre glass 

mesh to the floor.

Do not store tiles or heavy objects on the mat while tiling. Wait for 8 days to allow 

the adhesive to dry before you switch on the system.

FINALLY TEST THE RESISTANCE OF THE HEATER(S) ONCE TILING IS COMPLETE. 

Installation cont’d

5

6

7

9

Summary of Contents for PVC

Page 1: ...0845 345 2288 IMPORTANT Read this manual before attempting to install the heater Incorrect installation could damage the heater and will invalidate your warranty Complete and submit your warranty form online at www warmup co uk The world s best selling floor heating brand ...

Page 2: ...e ensure that you have the correct heater s for the area you wish to heat Warmup plc the manufacturer of the Warmup Undertile Heating System accepts no liability expressed or implied for any loss or consequential damage suffered as a result of installations which in any way contravene the instructions that follow It is important that before during and after installation that all requirements are m...

Page 3: ...the mat Switch on the installed mat until 8 days after fitting to allow the tile adhesive to dry completely Install the mat in temperatures less than 5 C Bend the heating cable under 25mm radius Use the heating system to dry out levelling compound or adhesive Tape over the end cap or manufactured joint Attempt a DIY repair if you damage the heater Contact Warmup on 0845 345 2288 If you accidentall...

Page 4: ...e tiles As with all electrical projects all mains electrical connections must be undertaken by a certified electrician All work must conform to current IEE Wiring Regulations The Underfloor heating must be controlled via a floor sensor thermostat at all times Installing a Residual Current Device RCD The Heating Mats must be wired via an 30mA RCD You must install a dedicated RCD if one is not alrea...

Page 5: ...t 3 1999 Concrete Subfloors Ensure you use an extruded polystyrene building or tile backer board Warmup Insulation Board if installing your mat onto a cement based floor Fixing the board should be as per the manufacturer s instructions About the mat 1 Concrete Timber Subfloor 2 Flexible Adhesive 3 Wamup Insulation Board 4 Warmup Underfloor Heating Mat 5 Flexible Adhesive Tile NOTE Warmup thermosta...

Page 6: ... problem please contact Warmup s Technical Team on 0845 345 2288 for guidance Floor Sensor Ensure that the floor sensor is tested before the final floor finish has been laid The floor sensor values can be found in the thermostat instructions When testing the floor sensor ensure that the meter can read up to 20k ohms 6 150W m2 200W m2 Model Size m2 Wattage Amps Resistance Model Size m2 Wattage Amps...

Page 7: ...as the proper room dimensions and that you have the correct size and proper number of mats Mats should run backwards and forwards between walls and obstructions as shown in the examples Depending on insulation air flow overall heat loss within the room additional heating may be required Before Installation Test Perform the first test following the steps described above to ensure that the mat has n...

Page 8: ... the Heater Before installing the heating mat perform the same test as described on page 6 to ensure that the heater has not been damaged during planning Step 3 Cut turn and affix the mat When you have marked the positions and planned the route of the mat on the floor start laying the mat cutting and turning where the marks have been made beginning at the location closest to the thermostat Be care...

Page 9: ... the subfloor When doing this take care not to damage the heating element Secure the power lead in place using tape but do not tape over the manufactured joint where the power supply cable meets the heating element The power lead will go into the electrical trunking conduit up to the thermostat It is possible to extend the power lead using twin and earth cable Note Instructions for fitting the War...

Page 10: ...rten the heating element Ensure that the entire heating elements including the joints are installed under the tiles in the installation The Heating element must be used in conjunction with a 30mA RCD Heater Model Resistance Before Resistance After Insulation Resistance Pass Floor sensor resistance This form must be completed as part of the Warmup Guarantee Ensure that the values are as per the ins...

Page 11: ...receipt should state the exact model that has been purchased and 2 only if the heater has been earthed and protected by a Residual Current Device RCD at all times Thermostats are guaranteed for a period of 3 YEARS from the date of purchase except as provided below The guarantee for the Warmup 3Ie thermostat can be upgraded to lifetime Contact Warmup for details 0845 345 2288 Neither guarantee cont...

Page 12: ...associated logos are trade marks Warmup Plc 2014 Regd TM Nos 1257724 4409934 4409926 5265707 E OE Warmup plc 702 704 Tudor Estate Abbey Road London NW10 7UW Web www warmup co uk Email uk warmup com Tel 0845 345 2288 Fax 0845 345 2299 ...

Reviews: