If you find that once the heating panel has been installed you have excess heating
panel, contact Warmup immediately on 0845 345 2288.
Do
NOT
cut the heating element to fit a zone or leave any of the heating panel
exposed behind units or fixtures.
If you are installing multiple heating panels they should be connected in parallel
via a junction box.
Install the temperature sensor supplied with the Warmup thermostat.
Fit the temperature sensor wire at least
300mm into the heated area. The sensor tip
should be centred between two of the heating
element runs.
Do
NOT
allow the sensor to touch or cross any
of the heating element at any time.
The sensor tip must
NOT
be covered with tape as this may result in an incorrect
temperature reading.
If necessary the sensor may be extended up to 50 metres to the thermostat
location. The sensor must be run in a separate conduit -it must be separated from
other cabling.
Before tiling test the heater and temperature sensor. Use a 20k -200k ohms setting
when testing the sensor.
At room temperature you should get a reading between 8-12K ohms.