7
Location of the heating panels
When installing the Warmup wall heating panel it is important that the installation
is design and installed carefully to avoid any harmful influence between the heating
system and other electrical and non electrical installations.
When installing the heating element near
other electrical installations it is important to
that the heating element does not affect the
electrical installation such as reducing the
current carrying capacity of cables from other
circuits due to the high ambient temperature
caused by the heating system. In order to
avoid this leave a perimeter of 200mm around
the edge of the wall.
In order to prevent the heating element from causing high temperatures to
adjacent materials always ensure that the heating panel is at least 10mm from
ignitable structures.
Heat Free Zones
When designing the areas to be covered it is important that heat free zones are
allocated for areas where drilling or fixings may occur.
Thermal Blocking
Do not fix items to the wall over the heated areas that may block the heat . Fittings
may only be installed into the non heated areas.
Draw a plan
In order for your installation to run as smoothly as possible and to ensure that
the location of the heating panels can clearly be identified at a later date, a plan
showing exact locations with measurements MUST be drawn.
This MUST be kept along with the heater information, test records, operating guides
and any other relevant documentation required, at or near the consumer unit.
Planning the installation
200mm
200mm
200mm
200mm
Summary of Contents for WHP1
Page 17: ...17 Wall Plan ...