UPS-Division
Operating Manual Wärtsilä JOVYLINE 625/1200/2200 BAX 3522 E page 4
1. Technical
data
1.1 Table 1: Typespecifical data
UPS (nominal power)
625 VA
1200 VA
2200 VA
Input voltage / mains voltage
230 V +20% -25%
Mains frequency
50 / 60 Hz
5% (automatic switch-over)
Output voltage
230V
Output frequency
50 / 60 Hz
0,5% (at battery operation)
Voltage regulation of the output
voltage
AVR increases the output voltage by 15% over input voltage, if the
input voltage sinks within –9% up to – 25%. AVR decreases the output
voltage by 13% compared with the input voltage, if the input voltage
increases 9% up to +25%
Time for switch over
2-4 ms including detection time
10 Base-T Cable Port
network (UTP, RJ-45) compatible plugs
Protection against spikes
320 Joule, 2ms
Overload protection
UPS switches off after 110% overload for 60 sec. and
130% overload for 3 sec.
Short circuit protection
UPS switches off immediately or input protection gets released
Input protection
Protection against overload and short circuit
Type of battery
Lead battery, closed maintenance-poor
12V / 7Ah (JOVYLINE 625) 24V / 7Ah (JOVYLINE 1200 /
JOVYLINE 2200)
Charging duration battery
4 hours up to 90% of nominal capacity
Protection installations battery
Automatic selftest and protection against discharging, display for
defect batteries
Autonomy time
10-30 min. (in dependency on the computer load)
Weight UPS
6,5 kg
13,4 kg
15,9 kg
Dimension (w x h x d) in mm
97 x 320 x 135
130 x 382 x 192
130 x 382 x 192
Mains input connection
Connection acc. IEC 320
Alarm, battery charging
Slow bleeping tone (ca. 0,47Hz)
Alarm, battery discharged
Quick bleeping-tone (ca. 1,824Hz)
Alarm, overload
Permanent sound
Interface RS-232
Bi-directional com. Port
Rules for construction
security: VDE, TÜV, CE ,
Surrounding terms
Placing
1000m above sea level acc. to EN 62040-3
Surrounding terms
General
humidity 0 - 95% non condensing, acc. to table DIN 40040
0-48°C
Decibel level acc. to ISO 7779
< 40 dbA
Technical modifications be possible