Unloading:
In normal operation the load should not be reduced from high load to low load (much) faster
than the load is increased. Crash stop can be recognised with a large lever movement form
ahead to astern within some seconds, which overrides normal load reduction. In the
manoeuvring range, typically below 50% load, the load can be reduced without rate limitation.
Fig 2-3
Maximum Loading and Unloading capacity in gas
2.2.2.1
Maximum instant load steps
The electrical system must be designed so that tripping of breakers can be safely handled.
This requires that the engines are protected from load steps exceeding their maximum load
acceptance capability. If fast load shedding is complicated to implement or undesired, the
instant load step capacity can be increased with a fast acting signal that requests transfer to
diesel mode.
2-4
DBAD209883
Wärtsilä 46DF Product Guide
2. Operating Ranges
Summary of Contents for 46DF
Page 1: ...W rtsil 46DF PRODUCT GUIDE...
Page 4: ...This page intentionally left blank...
Page 8: ...This page intentionally left blank...
Page 16: ...This page intentionally left blank...
Page 118: ...This page intentionally left blank...
Page 140: ...This page intentionally left blank...
Page 148: ...This page intentionally left blank...
Page 174: ...This page intentionally left blank...
Page 186: ...This page intentionally left blank...
Page 198: ...This page intentionally left blank...
Page 206: ...This page intentionally left blank...
Page 214: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 230: ...This page intentionally left blank...
Page 234: ...This page intentionally left blank...
Page 236: ...This page intentionally left blank...
Page 241: ...Fig 21 7 List of symbols DAAF406507 7 DBAD209883 21 5 21 ANNEX W rtsil 46DF Product Guide...