Pipes between engine and jacket water preheater
5.6
Local gauges
Local thermometers should be installed wherever a new temperature occurs, i.e. before and
after heat exchangers, etc.
Pressure gauges should be installed on the suction and discharge side of each pump.
5.7
Cleaning procedures
Instructions shall be given at an early stage to manufacturers and fitters how different piping
systems shall be treated, cleaned and protected.
5.7.1
Cleanliness during pipe installation
All piping must be verified to be clean before lifting it onboard for installation. During the
construction time uncompleted piping systems shall be maintained clean. Open pipe ends
should be temporarily closed. Possible debris shall be removed with a suitable method. All
tanks must be inspected and found clean before filling up with fuel, oil or water.
Piping cleaning methods are summarised in table below:
Table 5-3
Pipe cleaning
Methods
System
A,B,C,D,F
Fuel oil
A,B,C,D,F
Lubricating oil
A,B,C
Starting air
A,B,C
Cooling water
A,B,C
Exhaust gas
A,B,C
Charge air
1)
In case of carbon steel pipes
Methods applied during prefabrication of pipe spools
A = Washing with alkaline solution in hot water at 80°C for degreasing (only if pipes have been greased)
B = Removal of rust and scale with steel brush (not required for seamless precision tubes)
D = Pickling (not required for seamless precision tubes)
Methods applied after installation onboard
C = Purging with compressed air
F = Flushing
5.7.2
Fuel oil pipes
Before start up of the engines, all the external piping between the day tanks and the engines
must be flushed in order to remove any foreign particles such as welding slag.
Disconnect all the fuel pipes at the engine inlet and outlet . Install a temporary pipe or hose
to connect the supply line to the return line, bypassing the engine. The pump used for flushing
should have high enough capacity to ensure highly turbulent flow, minimum same as the max
5-4
DAAB605814
Wärtsilä 46F Product Guide
5. Piping Design, Treatment and Installation
Summary of Contents for 46F Series
Page 1: ...Wärtsilä 46F PRODUCT GUIDE ...
Page 4: ...This page intentionally left blank ...
Page 8: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 86: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 154: ...This page intentionally left blank ...
Page 162: ...This page intentionally left blank ...
Page 170: ...This page intentionally left blank ...
Page 176: ...This page intentionally left blank ...
Page 194: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 207: ...Fig 21 7 List of symbols DAAF406507 7 DAAB605814 21 5 21 ANNEX Wärtsilä 46F Product Guide ...