Wärtsilä JOVYTEC PMS 2002K / 3002K   BAX 4837E  

 - 11 -

 

 

 

WÄRTSILÄ JOVYTEC PMS 3002K (230V – Version) 

 

Output 

cos 

 0,7 ind. 

3000VA / 2100W 

 

Network supply 

Voltage 

230V  

Input voltage ranges  

168V - 276V (0-100% load) 

140 - 159V (0-70% load) 

120 - 139V (0-40% load) 

Current 

11A 

Frequency 

50Hz ±3Hz or 60Hz ±3Hz 

Phase 

Single phase 

Power factor 

0.98 

External 

 

fuse protection 

D01/16A 

 

Battery 

(installed in the 

battery rack 

POWERPACK 

S 1002) 

Direct current link voltage 

72 V 

Backup time 

(1 Battery unit) 

5min. @ 100% load 

6min. @ 80% load 

12min. @ 50% load 

Backup time 

(2 Battery units) 

15min. @ 100% load 

18min. @ 80% load 

32min. @ 50% load 

Backup time 

(3 Battery units) 

25min. @ 100% load 

28min. @ 80% load 

58min. @ 50% load 

Type 

Maintenance-free, VRLA batteries 

Charging time 

< 8 hours for a 90% recharge 

 

Output 

Voltage 

230V standard (208V / 220V / 240V selectable at the panel) 

Frequency 

Automatic adjustment by means of internal control-logic of UPS 

Power factor 

cos 

0,7 ind. 

Phase 

Single phase 

Distortion factor 

< 3% for a linear load 

Overload behaviour  

100 to 125% for 60 seconds 

125 – 150% for 10 seconds 

Crest Factor 

3 : 1 

 

Efficiency 

AC to AC 

88 - 98% according to the operating mode 

 

Load transfer 

characteristic 

Power failure 

0 ms 

Overload switching 

Automatic transfer of the load 

 

Noise level 

At an approx distance of  

1 metre 

< 53dB(A) 

 

Environment 

Temperature 

0°C to 40°C 

+15 … +25°C (recommended) 

Air humidity 

0% to 95%, non-condensing 

Storage at  … 

20°C (recommended) 

-20 .... +50°C (without battery) 

 

Interfaces 

RS 232 interface 

 

Optional:  

USB   interface 

Relay card 

AS/400 - adapter 

SNMP - adapter 

Supports power management and diagnosis such as BATTERY LOW, UPS 

ON/OFF 

Software is compatible with operating systems such as: Windows 

95/98/NT/2000/XP, Novell, Unix, etc current operating systems. 

 

Dimensions 

UPS 

 

rack 

Width 

19“ 

Depth 

425 mm 

Height 

2RU 

Dimensions 

battery rack 

Width 

19“ 

Depth 

425 mm 

Height 

2RU 

 

Weight of UPS 

UPS 

approx. 11 kg 

Weight of UPS 

incl. battery 

UPS incl. 1 Batteryunit 

about 22.5 kg 

Scope of delivery  Hardware/software 

UPS unit WÄRTSILÄ JOVYTEC PMS 3002K 

Battery rack POWERPACK S 1002 (according to backup time: 1-3) 

Manual BAX 4837E 

Interface cable 

Software UPSMON (No support) 

Summary of Contents for BAX 4837

Page 1: ...l un I Jet _________ __ Jovyatlas Jovytec PMS 2002K 3002K https www uni jet com catalog istochniki besperebojnogo pitaniya on line ibp 1 kva 10kva jovytec pms 2002k 3002k html...

Page 2: ...BAX 4837 Operating manual W rtsil JOVYTEC PMS 2002K 3002K...

Page 3: ...JOVYTEC PMS 2002K 3002K BAX 4837E 2 Index Date Name Issue 0 2013 04 03 A Heller Original 1 2014 11 07 Chr Fechteler 14 608 2 2015 11 12 Chr Fechteler 15 609 3 2015 12 04 Chr Fechteler 15 651 4 5 6 7...

Page 4: ...are not part of the contract but simply serve as a source of information W rtsil JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in t...

Page 5: ...W 15 5 3 INSTALLATION 16 6 ELECTRICAL CONNECTION 17 6 2 COMMISSIONING THE UPS UNIT 18 6 3 SHUTTING DOWN THE UPS UNIT 18 7 OPERATING AND INDICATING ELEMENTS 19 7 1 LED AND FUNCTION KEYS 19 7 2 PARAMETE...

Page 6: ...SIGNMENT OF THE RS232 INTERFACE 25 9 3 USB PORT OPTIONAL 26 10 SPECIAL EQUIPMENT 26 10 1 ELECTRONIC STOP FUNCTION 26 11 MANUAL BYPASS OPTIONAL 26 12 POTENTIAL FREE SIGNALS FROM THE RELAY CARD OPTIONAL...

Page 7: ...l discharging voltage is not reached 1 General notes The device may only be opened by trained specialists The system is to be connected up and earthed according to VDE regulations Provisions of the lo...

Page 8: ...on During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating volt...

Page 9: ...eans that in the case of a power failure the connected consumers will no longer be supplied with power Figure 3 Block diagram Fault in the inverter Manual bypass service bypass If there is a fault in...

Page 10: ...to 125 for 60 seconds 125 150 for 10 seconds Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operating mode Load transfer characteristic Power failure 0 ms Overload switching Automatic tra...

Page 11: ...ar load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10 seconds Crest Factor 3 1 Efficiency AC to AC 88 95 according to the operating mode Load transfer characteristic Power failure 0 ms O...

Page 12: ...inear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10 seconds Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operating mode Load transfer characteristic Power failure 0 m...

Page 13: ...W rtsil JOVYTEC PMS 2002K 3002K BAX 4837E 12 2He 19 428 425 5 Dimensions and views Picture 1 Front view Picture 2 Top view...

Page 14: ...LED operation lights green if the UPS is switched on 9 LED operation lights green when in UPS and bypass mode and signalises that the output voltage is present 10 LED battery operation lights yellow...

Page 15: ...interface Relay board or SNMP 2 RS 232 Interface 3 Cover for optional USB Interface 4 Fan 5 Battery jack external battery pack l 6 UPS output 7 UPS Input C13 plug 8 Input fuse 15A 2002K Input fuse au...

Page 16: ...C PMS 2002K 3002K BAX 4837E 15 5 2 Powerpack Front and Rear View Picture 10 Front view 1 2 Picture 11 Rear view Position Designation 1 Connecting jack for an optional additional battery pack 2 Battery...

Page 17: ...W rtsil JOVYTEC PMS 2002K 3002K BAX 4837E 16 5 3 Installation For installation the two supplied angles are to be mounted on both sides as shown on the sketch...

Page 18: ...connecting up work is now complete P L E A S E N O T E Only trained personnel are allowed to work on the UPS unit Observe all corresponding safety regulations Marking of cables is to be according to...

Page 19: ...while pressing the ON OFF button and the message Switching off soon appears in the display and then the message UPS OFF The UPS unit is now shut down Please note The internal fans of the UPS will con...

Page 20: ...ch as the output voltage etc The formalism is as follows Press the FUNC key on a running UPS unit for 2 seconds to start the menu for the UPS unit parameters Pressing of the ENTER button selects the p...

Page 21: ...f the UPS BAT VOLT 81V Battery voltage of the battery pack O P LOAD 80 Utilisation of the UPS as a percentage O P W 1400W Output in Watts O P VA 2000VA Output in VA O P CURR 13A Output current in A BA...

Page 22: ...UPS will switch to bypass if the preset parameters are not maintained ON OFF OFF Operating mode setting HE mode setting Online Offline mode ON OFF OFF Setting for a permanent manual bypass Man bypass...

Page 23: ...ere adopted in that the display shows High Efficiency The UPS unit will start again automatically after restoration of the mains power and starts in the preset mode after a long period of power loss w...

Page 24: ...Result The UPS unit will not switch to bypass not activated since the preset parameter has not been maintained and the bypass is deactivated 7 8 2 Free running ON bypass activated Example Input volta...

Page 25: ...ary The UPS switches again to normal operation after a successful battery test Overcharging over charge Continuous tone The batteries are over charged Battery charge voltage too high Contact the servi...

Page 26: ...UPS unit can be monitored and checked by a computer through the use of special software Switching off of the UPS unit in the case of power failure is possible 9 1 Connecting the UPS to the computer T...

Page 27: ...the UPS unit If the electronic STOP functionality is to be used then the bridge should be removed on the plug and an external switch opener clamped to the rear plug Actuation of the external electroni...

Page 28: ...to be switched voltage free and the UPS unit shuts down In order to supply consumers with voltage again it is necessary for the electronic STOP switch to be reset and for the UPS to be restarted There...

Page 29: ...W rtsil JOVYTEC PMS 2002K 3002K BAX 4837E 28...

Page 30: ...er continues to run automatically until the battery is charged up Restoration of mains power after total discharge of the battery At the end of the backup time the inverter switches off automatically...

Page 31: ...life of batteries 10 12 years 6 9 years 3 5 years Temperature Expected working life of batteries 20 C 12 years 9 years 5 years 30 C 5 years 4 years 2 5 years 40 C 2 5 years 2 years 1 25 years 13 4 Ins...

Page 32: ...Proceed as follows to replace the battery Note Exchanging the battery could lead to a power outage on the output when the input power fails during the procedure 1 Disconnect all battery racks form the...

Page 33: ...___________________________________________________________________________________ ______________________________________________________________________________________ _____________________________...

Reviews: